2. WIRING  

- Another important difference in the replacement of an “ESU” model with a new “S” 

series humidifier is the wiring connections. On the “ESU” the humidity control was connected to the
two  ‘WHITE” wires on the molded plug.  When upgrading to the “S” series, simply cut the two 
white wires and connect them to the two “H” terminals on the top of the front cover. 

The blower (fan) interlock was connected via the two red wires on the old “ESU” model and usually 
incorporated a field installed transformer and interlocking relay.  Just cut the two red wires and 
connect them to the “R” and “G2” terminals on the top of the front cover. In this method you can 
reuse the field relay and transformer which were originally installed with the ESU.

If this is a new install then you can fully utilize the on board relay provided with the “S” series 
humidifier and interlock your blower “fan” by following  the low voltage diagram. There is no need 
to install a separate transformer or relay.

DO NOT plug the molex connector  from the old “ESU”  humidifier,  into the socket on the side of
the front  cover on the new “S”  series humidifier.  That  socket connection  is now reserved for the
automatic  drain  valve only. Doing so will damage  the unit  and  void the warranty.

2

S 2000 &  S 2020 T ypi cal  W i r i ng

and B l ower  I nter l ock  Di agr am

           Furnace 

             S2000 & S2020 Humidifier

  Humidistat

G1

R

G2

H

H

Typical

Thermostat

G

Y

W

R

G

Y

W

R

H eat &  Cool  S ystem

      

Field Controls Humidifiers

AN-137 Replacement Instructions for
Models ESU14 & ESU20

SUPPLEMENT TO THE ELECTRONIC STEAM 

POWER HUMIDIFIERS MODEL #S2000 AND S2020