background image

page 2 of 12

Diagrams A and B and Table 1 show the maximum equivalent length and size of duct pipe that should be used 
when installing the CAS system. Using these charts will help ensure that the proper amount of air is drawn 
into the structure as needed by the appliance. The defi ned regions shown correspond to the CAS's airfl ow 
characteristics when using 4" and 6" diameter sheet metal duct pipe and the included orifi ce ring. Follow the 
guidelines below to properly size and setup the CAS.

1. Determine the maximum input fi ring rate of the appliance, or the maximum total fi ring rate of multiple 

appliances that will be used.

2.  Position the motorized CAS unit according to the guidelines in the Installation section.

3.  Determine where the intake air vent hood will be located based on the recommendations in the Installation

      section.

4.  The CAS is equipped with a High/Low motor speed control switch. When calculating the maximum equivalent 

feet, determine which speed is appropriate for the application. (Refer to Diagram A or B or Table 1)

5.  Calculate the total equivalent length of duct pipe including elbows and fi ttings needed to connect the CAS 

unit to the vent hood. (Refer to Diagram A or B or Table 1)

6. On Diagram A or B, locate the point that corresponds to the fi ring rate along the horizontal axis and the 

equivalent length of the duct pipe along the vertical axis, if using for make up air.

7. The point should fall within one of the three regions on the table. Each region corresponds to a duct pipe 

diameter of 4", 4" using the orifi ce ring, and 6" respectively.

GENERAL SYSTEM OPERATION

1.  The thermostat (wall thermostat, or aquastat) calls for heat and energizes a relay which activates the CAS 

unit. After the CAS fan has come up to speed and air fl ow into the CAS inlet is estabished, an internal 
air pressure switch closes and completes the circuit to allow the burner to fi re. If the appliance is power 
vented, the venter and CAS activate simultaneously. After the CAS and power venter have come up to 
speed, a pressure switch in the power venter control also closes and allows the appliance to fi re.

2.  After the heating requirement has been satisfi ed, the thermostat circuit will open and deactivate the 

burner and CAS unit.

3.  For power vented systems with a post purge device, the power venter and CAS operate for a period of 

time after the burner has shut off  to purge remaining fl ue gases from the vent system.

INSTALLATION SAFETY INSTRUCTIONS

CAUTION: This device must be installed by a qualifi ed installer in accordance with the manufacturer’s 
installation instructions.

1.  This combustion air system must be installed by a qualifi ed installer. “Qualifi ed Installer” shall mean an 

individual who has been properly trained or a licensed installer.

2.  Plan the system layout before installation to avoid the possibility of accidental contact with concealed 

wiring or plumbing inside walls.

3.  Disconnect power supply before making wiring connections to prevent electrical shock and 

equipment damage.

SIZING AND SETUP

P/N 46284600 Rev L 09/19

Summary of Contents for FAN IN A CAN CAS4

Page 1: ...24 control kit per each additional appliance see note The CAS unit mechanically draws air into a structure and disperses it near the combustion air intake of an appliance Refer to Diagrams A and B fo...

Page 2: ...l within one of the three regions on the table Each region corresponds to a duct pipe diameter of 4 4 using the orifice ring and 6 respectively GENERAL SYSTEM OPERATION 1 The thermostat wall thermosta...

Page 3: ...matter which way the Orifice Ring is turned as long as it is pushed down against the ledge completely Use 4 diameter pipe to connect the vent hood and the CAS unit TOTAL INPUT OF APPLIANCE TOTAL INPU...

Page 4: ...00 250 300 350 400 GAS INPUT FIRING RATE 1000 BTU hr MAX EQUIVALENT DUCT LENGTH ft 0 0 0 50 1 00 1 50 2 00 2 50 OIL INPUT FIRING RATE gallons per hour 1 gallon oil hr 140 000 BTU hr 6 Duct Hood 4 Duct...

Page 5: ...a power vented exhaust outlet and should be on the same wall The intake air hood should be a minimum of 1 above grade or snowlines where applicable INSTALLATION OF INTAKE AIR HOOD After determining t...

Page 6: ...be attached to the green colored ground screw near the wire terminals The following sections describe the most common applications The references to various series of control kits implies that any ki...

Page 7: ...page 7 of 12 Figure 5 Power Vent Single 24V Furnace Figure 6 Chimney Vent 24V Furnace and 30mV Water Heater With CK 20FV or CK 20FG P N 46284600 Rev L 09 19...

Page 8: ...page 8 of 12 Figure 7 Chimney Vent 24V Boiler Figure 8 Power Vent Single 24V Boiler P N 46284600 Rev L 09 19...

Page 9: ...page 9 of 12 Figure 9 Chimney Vent Two 24V Gas Appliances With CAC 24 P N 46284600 Rev L 09 19...

Page 10: ...page 10 of 12 Figure 10 One Power Venter Two 24V Gas Appliances P N 46284600 Rev L 09 19...

Page 11: ...nadequate air flow is allowed into the inlet of the CAS 4 Clear any obstructions if present from the inlet of the vent hood and the outlet of the CAS unit 5 Periodically the fan blade chamber may need...

Page 12: ...ed and printed from the Field Controls website www fieldcontrols com WARRANTY WARRANTY For warranty information about this or any Field Controls product visit For warranty information about this or an...

Reviews: