WARNING: never expose eyes or skin to UVC light from any source. Looking directly at the UVC light may cause permanent eye damage or blindness. 

Never operate the UV-Aire™ AirPurifying System out of the plenum. Avoid touching the glass portion of the lamp with your hands.

14.  Identify an area of the access panel or other area of the equipment or duct through which the lamp may 

be seen. Verify that the surface is free of dirt, oil, and other contaminants, peel of the label backing and apply 

the Safety label to the surface such that the warning information is clearly visible (see Figure 8).
15.  Drill a 3/8” hole through the center of the Safety Label, where indicated by the dashed circle (see figure 7).
16.   Snap the clear plastic Safety Viewport into the hole (see Figure 8).  The lamp may be safely viewed 

through the viewport while it is lit.
17.   Verify that all electrical connections are tight and that the lamp and bracket is secure.

18.   Replace all access panels and other items that may have been removed during the installation, such as 

electrical box covers, etc. 

19.   Verify that the Safety Viewport is securely fastened in the hole drilled through the Safety Label.

WARNING: BEFORE RESTORING POWER TO THE HVAC SYSTEM OR THE TRANSFORMER POWER SOURCE, VERIFY 
THAT NO OPENINGS EXIST THROUGH WHICH UVC RAYS FROM THE LAMP MAY ESCAPE.  VERIFY THAT ALL 
ACCESS PANELS AND DUCTWORK ETC. HAVE BEEN REPLACED AND SEALED IF NECESSARY, AND THAT THE 
SAFETY VIEW PORT IS SECURELY FASTENED IN PLACE.

20.   Restore power to the HVAC system and the transformer power source.  Look through the Safety Viewport 

to verify that the lamp is lit.

BRACKET MOUNT INSTALLATION THROUGH A-COIL DELTA PLATE OR PLENUM

If the lamp is to be mounted externally on the plenum or an air duct, or if the 

lamp is to be mounted through a delta plate (covers the end of A-coil in certain air 
handler designs), follow these steps for installation:

1.   Separate the lamp mounting portion of the Lamp Bracket from the remainder 

of the lamp bracket (see Figure 4), by bending back and forth or cut with snips or 

hacksaw.

2.  Attach the shield to the separated bracket, on the side opposite from the 
lamp mounting studs (see Figure 5), if it is to be used.  Any of the four attachment 

positions may be used.
3.  Insert the lamp through the oval hole in the bracket and shield base, and attach 

to the mounting studs using the supplied #8-32 locking nuts (see Figure 5).  Do not 
use the supplied #8-32 wingnuts, unless the lamp is to be installed inside an air 

handler or other equipment or structure requiring the use of a tool to access.

4.  Mark the location for the lamp, and drill or cut a 2” round hole (may be an oval hole 2” x 1” 
if the shield is not used) in the mounting surface, using care to avoid damage to equipment or 
concealed wiring.  If the lamp is to be mounted on duct board, fabricate a mounting surface by cutting a 6” x 
6” square of suitable sheet metal.  Cut the hole for the lamp in the sheet metal and the duct board, and tape 

the sheet metal securely to the duct board using mastic-backed metal tape.

5.  Insert the lamp through the hole, orient the lamp such that it presents the least obstruction to airflow 

or that the shield is in proper position, and secure the bracket to the mounting surface using three of the 
supplied sheet-metal screws, or other appropriate fasteners.

6.  If mounting through the exterior of a plenum or air duct, use metal duct sealing tape (not included) to tape 

around the edges of the mounting bracket, to prevent UVC rays from escaping and 
prevent duct leakage. 
7.  Position the cable clamp installed on the Lamp Cable such that the clamp 
hole is aligned with the fourth hole in the bracket, and install the fourth screw or 

fastener through the clamp and bracket, into the mounting surface (see Figure 6).  

Note: This step is important to preclude the inadvertent removal of the lamp from 
the bracket before disconnecting the lamp cable from the lamp.

Figure 4

Figure 5

Figure 6

Summary of Contents for FlexMountUV UV-AIRE Series

Page 1: ... SYSTEM Model UV 13FM 17FM UV C light inhibits the growth and reproduction of germs and bacteria that circulate through a homes heating and air conditioning system The treatment is a safe silent and proven way to make your home a healthier place to live ITEMS INCLUDED IN KIT Twin Tube High Output UVC Lamp 24 VAC Ballast UL listed with Lamp Cable connector Lamp Cable with connector FlexMount Articu...

Page 2: ... condition nor for use in the mitigation treatment or prevention of any disease or condition INDICATION FOR USE There are different size units available depending on the tonnage of your HVAC system See chart below for determining the needs of your home The FlexMount UV Aire system is provided with a unique patent pending magnetically attached Mounting Bracket Assembly The mounting bracket assembly...

Page 3: ...nstream from the air filter For optimum cleaning effect on the A coil mount the unit above or below the A coil as close as possible while still illuminating the entire surface of the coil See Figure 1 2 Clean the mounting surface with degreaser and let dry The mounting surface must be clean and dry 3 Attach the Shield to the Mounting Bracket Assembly if it is to be used by bending the tabs on the ...

Page 4: ... that the 120V transformer power source be wired through a safety disconnect switch such as a door switch that will disconnect power to the transformer if the access panel to the UVC lamp installation area is removed see Wiring Diagram If such a switch is not present on the equipment it is recommended that a door interlock switch not included min 3A 24VAC rating be installed and wired into the 24V...

Page 5: ...hese steps for installation 1 Separate the lamp mounting portion of the Lamp Bracket from the remainder of the lamp bracket see Figure 4 by bending back and forth or cut with snips or hacksaw 2 Attach the shield to the separated bracket on the side opposite from the lamp mounting studs see Figure 5 if it is to be used Any of the four attachment positions may be used 3 Insert the lamp through the o...

Page 6: ...XTERNALLY ON A PLENUM OR AIR DUCT DISCONNECT THE LAMP CABLE FROM THE LAMP BEFORE REMOVING THE LAMP FROM THE EXTERNAL MOUNT BRACKET VERIFY THAT THE LAMP IS NOT LIT BY LOOKING THROUGH THE SAFETY VIEWPORT BEFORE REMOVING ANY ACCESS PANELS OR THE LAMP FROM THE EXTERNAL MOUNT BRACKET 1 Verify that the lamp is not lit by looking through the safety viewport 2 Disconnect the Lamp Cable connector from end ...

Page 7: ...e glass portion of the lamp with your hands TROUBLESHOOTING GUIDE 1 If the lamp does not light up replace the lamp 2 If the lamp still does not light up after replacing the lamp replace ballast REPLACEMENT PARTS LIST MODEL LAMP P N BALLAST P N UV 13FM 46632513 46635900 UV 17FM 46632517 OPTIONAL ACCESSORY PARTS LIST MODEL DESCRIPTION PART NUMBER TR50VA Transformer 120 208 240V Primary 24VAC 50 VA U...

Page 8: ... 252 522 3031 Fax 252 522 0214 www fieldcontrols com Field Controls LLC P N 46631000 Rev A 7 15 Warranty For warranty information about this or any Field Controls product visit www fieldcontrols com warranty ...

Reviews: