FS-8700-48 Fike Cheetah Manual
Page 12 of 36
FieldServer Technologies
1991 Tarob Court Milpitas, California 95035 USA
Web
: www.fieldserver.com
Tel
: (408) 262 2299
Fax
: (408) 262 2269
Toll Free
: (888) 509 1970
: support@fieldserver.com
5.2
Client Side Node Parameters
Section Title
Nodes
Column Title
Function
Legal Values
Node_Name
Provide name for node
Up to 32 alphanumeric characters
Protocol
Specify protocol used
Cheetah
Port
Specify which port the device is connected to the
FieldServer
P1-P8, R1-R2
3
PLC_Type*
This parameter tells the driver what type of panel
you are connecting to. If not specified, the driver
expects a legacy Cheetah panel.
Cybercat ,
Cheetah
Example
// Client Side Nodes
Nodes
Node_Name
, Protocol , Port , PLC_Type
Cheet_Master1 , Cheetah , P1
, Cheetah
5.3
Client Side Map Descriptor Parameters
5.3.1
FieldServer Specific Map Descriptor Parameters
Column Title
Function
Legal Values
Map_Descriptor_Name Name of this Map Descriptor
Up to 32 alphanumeric characters
Data_Array_Name
Name of Data Array where data is to be
stored in the FieldServer
One of the Data Array names from
Section 4.
Data_Array_Offset
Starting location in Data Array
0 to (Data_Array_Length-1) as specified
in Section 4.
Function
Function of Client Map Descriptor
Passive
Node_Name
Provide name for Node
Up to 32 alphanumeric characters
3
Not all ports shown are necessarily supported by the hardware. Consult the appropriate Instruction manual for details of the ports available
on specific hardware.
Set PLC_Type to Cybercat
for Xi Panels