The following limitations to older firmware have been identified. FieldServer is unable to correlate this change
with a particular Fike firmware version number at the current time.
Messages 1.1 and 6.0 (graphcis update msg) are sent by older panels. Only message 6.0 contains information that
can be used by the driver to reflect zone and device states. The 6.0 message is sent infrequently (typically 1 in 60
messages) and this results in a zone/device state update every few minutes.
Appendix B.1.1.
Message 6.0 limitations
Can only report data for 127 zones. Data is limited to Alarm, Trouble, Pre-Discharge and Released states
Can only report data for 127 devices on loops 1-4. Data is limited to Alarm, Trouble states.
Appendix B.1.2.
Message 1.1 - Older firmware
No useful information about zones or devices.
Appendix B.1.3.
Message 1.1 - Newer Firmware
Supports zones 1-240. For zones the following states are reported: Abort, Trouble, Supervisory, Disabled,
Pre-alarm, Alarm, Pre-Discharge, Released, Processed.
Supports devices 1-127 on loops 1-4. For devices the following states are reported: Alarm, Pre-Alarm and
Trouble
Appendix B.2.
Fike XI Panel Limitations and capabilities
The XI panels send messages which contain zone and device data. The message is known by Fike as a '1.2'
message.
The message reports if a device is normal, alarm, trouble or in a pre-discharge state. 256 Devices on loops 1-4 are
reported. 255 Zones report Process, Trouble, Supervisory, Disable, Pre-Alarm, Alarm states.