Setting the MAC Address
for BACnet MS/TP for the
ProtoNode RER (FPC-N34)
• Only 1 MAC address is set for the ProtoNode
regardless of how many Raypak devices are
connected to the ProtoNode.
• Set the BACnet MS/TP MAC addresses between 1 to
127. This is so that the BMS Front End can find the
ProtoNode.
• Addresses from 128 to 255 are Slave Addresses
and cannot be discovered by BMS Front Ends that
support auto discovery of BACnet MS/TP devices.
Never set a BACnet MS/TP MAC Address from 128
to 255.
• Set DIP switches A0 – A7 to assign MAC Address for
BACnet MS/TP for the first Raypak device attached
to the ProtoNode.
• Please refer to "Address DIP Switch Settings" on
page 24 for the full range of addresses to set
Node-ID/Device Instance.
• When using Metasys N2 and Modbus TCP, the A
Bank of DIP switches are disabled and not used.
They should be set to OFF.
Figure 3. A0 through A7 DIP Switches
NOTE:
When setting DIP switches, please ensure that
power to the board is OFF.
Set Field RS-485 Baud
Rate for BACnet MS/TP on
ProtoNode RER (FPC-N34)
The serial baud rate setting between the BMS and the
Protonode has no impact on the communication baud
rate between the Versa IC Master and the Protonode. The
serial baud rate and Versa IC baud rate are not required
to match for communication to take place. The Versa IC
Master baud rate must always be set for 19K2 (19200)
to allow communication between the Versa IC Master and
the Protonode.
Setting the Serial Baud Rate (DIP
Switch B0 – B3) for BACnet MS/TP
• DIP Switches B0 – B3 can be used to set the serial
baud rate to match the baud rate provided by the
Building Management System for BACnet MS/TP.
• DIP Switches B0 – B3 are disabled on ProtoNode
LER (FPC-N35 LonWorks).
• The rate on the ProtoNode for Metasys is set for
9600. DIP Switches B0 – B3 are disabled for Metasys
N2 on ProtoNode RER (FPC-N34).
Figure 4. B0 through B3 DIP Switches
Baud
B0
B1
B2
B3
9600
On
On
On
Off
19200
Off
Off
Off
On
38400
On
On
Off
On
57600
Off
Off
On
On
76800
On
Off
On
On
Table D. “B” Bank DIP Switch Settings