FS-8700-73 BACnet MSTP Driver Manual
Page 10 of 48
FieldServer Technologies 1991 Tarob Court Milpitas, California 95035 USA Web: www.FieldServer.com
Tel: (408) 262-2299 Fax: (408) 262-2269 Toll Free: (888) 509-1970 email: support@FieldServer.com
Client Side Connection Parameters
Section Title
Connections
Column Title
Function
Legal Values
Port
Specify which port the device is connected to the FieldServer
P1-P8
1
, R1-R2
2
Baud
Specify baud rate
9600
, 19200, 38400,
76800
3
Parity*
Specify parity
Odd, Even,
None
Data_Bits*
Specify data bits
7
, 8
Stop_Bits*
Specify stop bits
1
, 2
Protocol
Specify protocol used
BACnet_MSTP
Poll Delay*
Time between internal polls
0-32000s,
1s
Timeout
Application logger timeout
30s
Max_Master*
Specify the highest MAC_Address for Master nodes. When
designing a MSTP network with multiple Master_Node devices,
allocate the MAC_Address settings on the different devices starting
at 1. This will allow you to specify a small Max_Master parameter
and hence will improve overall network performance
1-
127
Max_Info_Frames
Specify the maximum number of information frames the connection
may send before it must pass the token.
1
-65535
Example
//
Client Side Connections
Connections
Port , Baud
, Parity , Data_Bits , Stop_Bits , Protocol
, Poll_Delay , Timeout
R1
, 38400 , None
, 8
, 1
, BACnet_MSTP , 0.100s
, 30s
1 P1 to P8 will require the optional RS-485 converter (Part # 4301-00)
2 Not all ports shown are necessarily supported by the hardware. Consult the appropriate Instruction manual for details of the ports available
on specific hardware.
3 76800 baud is supported on the X30, X25 and ProtoCessor but not on the X20 and X40