4.1.4.
Map Descriptor Example 1 – Polling all available Controller Data
Map_Descriptor_Name,
Data_Array_Name,
Data_Array_Offset,
Function, Node_Name,
Gar_cmd,
Gar_data, Scan_Interval
GD_MBA1,
DA_Service_Data,
0,
RDBC,
Node_1,
Service_Data,
All,
1.0s
GD_MBA2,
DA_Oper_Mode,
0,
RDBC,
Node_1,
Operating_Mode,
All,
1.0s
GD_MBA3,
DA_Oper_Data,
0,
RDBC,
Node_1,
Operating_Data,
All,
1.0s
Data will be stored as follows:
Offset
Description
Units
DA_Service_Data
0
Advisories
see ES/RS2000 Controller spec
1-20
10x (Shutdown code / Hourmeter reading) pairs
see ES/RS2000 Controller spec
21
Current total runtime hourmeter reading
Hours
22
Current loaded runtime hourmeter reading
Hours
23-28
6x Current temp hourmeters [H1] – [H6]
Hours
29-34
6x Stored temp hourmeters [OH1] – [OH6]
Hours
35
Last maintenance A
Hours
36
Last maintenance B
Hours
37
Oilage
Unknown, see ES/RS2000 controller spec
Operating mode data
0
Operating mode indication
see ES/RS2000 Controller spec
1 Sequence
number
2
see ES/RS2000 Controller spec
2
Unit operating state
3
see ES/RS2000 Controller spec
Operating data
0
System pressure
divide by 16 for pressure in psig
1
Filter pressure
divide by 16 for pressure in psig
2
Discharge temperature
divide by 16 for temperature in degrees F
3
Reservoir temperature
divide by 16 for temperature in degrees F
2
ES V2.0X Controllers do not respond with this field
3
ES V2.0X Controllers do not respond with this field
The Gar_data field is set to “All”
indicating that all available data is
polled for.
The Gar_cmd field indicates the poll
is for Operating Data.
Note the active Read Block Continuous map descriptor
function responsible for polling the Controller.