Triangle Tube’s ProtoNode Startup Guide
Page 12 of 40
ProtoCessor
1991 Tarob Court Milpitas, California 95035 USA
Web
B0 B1 B2 B3
Figure 5: Baud Rate DIP Switches
2.3.5.1
Baud Rate DIP Switch Selection
•
DIP Switches B0 – B3 can be used to set the serial baud rate to match the baud rate provided by the
Building Management System for BACnet MS/TP.
•
DIP Switches B0 – B3 are disabled on ProtoNode FPC-N35 (FPC-N35 LonWorks).
•
The baud rate on ProtoNode for Metasys N2 is set for 9600. DIP Switches B0 – B3 are disabled for
Metasys N2 on ProtoNode FPC-N34.
NOTE:
When setting DIP Switches, please ensure that power to the board is OFF.
Baud B0 B1 B2 B3
9600
On On On Off
19200 Off Off Off On
38400 On On Off On
57600 Off Off On On
76800 On Off On On
Figure 6: Baud Rate
2.3.5 BACnet MS/TP (FPC-N34): Setting the Serial Baud Rate (DIP Switch B0 – B3)