Triangle Tube’s ProtoNode Startup Guide
Page 3 of 40
ProtoCessor
1991 Tarob Court Milpitas, California 95035 USA
Web
Quick Start Guide
1.
Record the information about the unit. (Section 2.1)
2.
Set the device’s Modbus Address for each of the devices that will be connected to ProtoNode FPC-N34 or
FPC-N35. (Section 2.2.2)
3.
Select a stored configuration and set field protocol MAC address/Node-ID/Device Instance, and baud rate.
(Section 2.3)
4.
Connect ProtoNode’s 6 pin RS-485 connector to the Modbus RS-485 network that is connected to each of
the devices. (Section 3.2)
5.
Connect FPC-N34
ProtoNode’s 3 pin RS-485 port to the Field Protocol cabling (Section 3.3),
or connect FPC-N35
ProtoNode’s 2 pin LonWorks port to the Field Protocol cabling. (Section 3.4)
6.
Connect Power to ProtoNode’s 6 pin connector. (Section 3.5)
7.
BACnet/IP or Modbus/TCP (FPC-N34): Use the ProtoNode’s embedded tool which is accessed with a
browser, referred to in this manual as the Web Configurator, to change the IP address. No changes to the
configuration file are necessary. (Section 4)
8.
LonWorks (FPC-N35): The ProtoNode must be commissioned on the LonWorks Network. This needs to be
done by the LonWorks administrator using a LonWorks Commissioning tool. (Section 5)