FLSC GB
184
Betriebsanleitung
•
73734 Esslingen - Fiessler Elektronik - Kastellstr.9
•
Doku Nr. 625 R.H.
Properties
Data
min.
type
max.
Arc suppressor (RC combination)
None
Low pass behaviour of load
(limit
frequency)
500
Hz
see test pulse data
Test pulse data
The outputs are tested cyclically
in the active state (short LOW
switching). When selecting the down-
stream control elements, ensure that
the test pulses do not produce a shut-
down with the parameters listed above.
OSSD 1
Test pulse width
55 µs
Test pulse frequency
Every 40 ms
OSSD 2
Test pulse width
55 µs or
460
µs
Test pulse frequency
Alternately every 40 ms
OSSD 1 and OSSD 2
Test pulse width
55 µs
Test pulse frequency
3 s
Cable specifications
Cable
length
30
m
Cable cross section
0.5 mm
2
Permissible line resistance
2.5 Ohm