3.0 SYSTEM COMPONENTS
3-12
Cheetah Xi Instal latio n Manual
UL S2203
Rev 9, 10/2016
P/N: 06-356
FM
3.5.3
TWO BUTTON REMOTE DISPLAY UNIT, P/N 10-2630
The Two Button Remote Display Unit (See Exhibit 3-21) provides
a 4x20 character LCD that mimics the host control panel’s
display. This allows system status information to be displayed at
a remote location. The unit is equipped with an internal piezo
and five status LEDs that provide instant audible and visual
notification of system status changes.
Refer to Fike document 06-610, for more information.
Note:
This unit can only be used on systems with panel
firmware V3.0 or higher.
3.5.4 ETHERNET MODULE, P/N 10-2627
ETHERNET MODULE W/ ENCLOSURE, P/N 10-074
The Ethernet Module (See Exhibit 3-22) provides a means to
connect the associated control panel to the Ethernet
(LAN/WAN). This connection allows the associated control
panel to send its history events to a remote monitoring panel that
can be located either on or off the protected premises.
The module can be mounted inside the Cheetah Xi enclosure or
it can be mounted remotely by ordering the custom mounting
enclosure.
Refer to Fike document 06-388, for more information.
3.5.5
MULTI-INTERFACE MODULE, P/N 10-2583
MULTI-INTERFACE MODULE W/ ENCLOSURE, P/N 10-069
The Multi-Interface Module (See Exhibit 3-23) provides an
interface point that allows connection of the following
ancillary devices to the host control panel:
1. Cheetah Classic panel – this interface allows the MIM
to act as a network card on the Cheetah Classic
network (feature not available in V7.00 firmware and
higher).
2. Parallel Printer – this interface allows a parallel printer
that is listed for “Fire Protective Signaling Use” to be
connected to the host control panel.
3. Serial Printer – this interface allows a Keltron 90-series
printer to be connected to the host control panel.
4. PC Graphic – this interface allows a PC Graphic
workstation to be connected to the host control panel.
The module can be mounted inside the Cheetah Xi
enclosure or it can be mounted remotely by ordering the
custom mounting enclosure.
Refer to Fike document 06-367, for more information.
Exhibit 3-21: Two Button
Remote Display Unit
Exhibi t 3-22: Ethernet Module
Exhibi t 3-23: Multi-Interface Module (MIM)