3.0 SYSTEM COMPONENTS
3-22
Cheetah Xi Instal latio n Manual
UL S2203
Rev 9, 10/2016
P/N: 06-356
FM
3.9.4
ADDRESSABL E AGENT RELEASE PULL STATION, P/N
20-1343
The Addressable Agent Release Pull Station (See Exhibit 3-47) is a
non-coded, dual-action manual release pull station. A Mini Monitor
Module is housed inside the pull station to provide an alarm initiating
input to the control panel. The pull station provides a manual means
of discharging an automatic fire extinguishing system.
Note:
No isolator version of this pull station is available.
3.9.5
SUPERVISED CONTROL MODULE, P/N 55-042
SUPERVISED CONTROL MODULE WITH ISOL ATOR,
P/N 55-047
The Supervised Control Module (See Exhibit 3-48) is used to switch
an external power supply or audio amplifier to notification appliances.
The module monitors the external power input for loss of power and
signals the Cheetah Xi panel accordingly. The module includes a tri-
color LED for instant indication of device status. The module is
capable of providing an optional pulsing output to signal different
states, when interfaced with the Cheetah Xi addressable loop. The
isolator version provides complete short circuit isolation for NFPA
Class X wiring. A module cover plate (not shown) is included with
the module.
In addition to interfacing with notification appliances, the SCM can
also be used to operate either of the following interfaces:
3.9.5.1
SOLENOID PROTECTION ASSEMBL Y, P/N 10-2360
The SCM can be connected to a single sprinkler solenoid rated up to
2 amps maximum at 24VDC. The Solenoid Protection Assembly
(See Exhibit 3-49)
must
be used when connecting a solenoid to the
SCM. Refer to Fike document 06-186 for compatible sprinkler
solenoids (Factory Mutual Approved Groups A-G).
Refer to Fike document 06-344, for more information.
3.9.5.2
MASTERBOX INTERFACE, P/N 10-2413
The Masterbox Interface (See Exhibit 3-50) provides the Cheetah Xi
control panel with the ability to activate a Local Energy Type
Auxiliary Fire Alarm System (as noted by NFPA 72). The Masterbox
Interface
must
be used in conjunction with a Supervised Control
Module (P/N 55-042).
Refer to Fike document 06-229, for more information.
Exhibit 3-48: Supervised
Control Module
Exhibit 3-49: Solenoid
Protection Assembly
Exhibit 3-47: Agent
Release Pull Statio n
Exhibi t 3-50: Masterbox Interface