4.0 INSTALLATION
4-18
Cheetah Xi Instal latio n Manual
UL S2203
Rev 9, 10/2016
P/N: 06-356
FM
4.16.6 NOTIFICATION APPLIANCE CIRCUIT WIRING (P10 & P11 )
P10 and P11 are two separate notification appliance circuits (NAC’s) that provide the ability to activate
compatible, UL-listed notification appliances listed in Fike document 06-186, “Device Compatibility manual”.
The NAC circuits are supervised, power-limited, and can be wired Class B (using 1.2K EOL) or Class A (no
EOL), as shown in Exhibits 4-21 and 4-22. Shielded wiring is not required, however if used, land at the panel
terminal block and pass through at each device similar to SLC device wiring.
The NACs can be configured to initiate the Gentex Commander Series or System Sensor SpectrAlert Series
sync protocol. This allows all devices (strobes and horns) connected to the circuit to operate in unison. It
also allows configuration for the audible devices to be silenced while the visual signals remain operational or
silence both audible and visual devices. This is accomplished without requiring purchase and installation of a
separate sync module. Both circuits must be programmed to use the same manufacturers sync pulse if this
option is used.
P10 OR P11
1.2K
EOL
POWER-LIMITED
AND SUPERVISED
TYPICAL
NOTIFICATION
APPLIANCE
SHIELD WIRE
Exhibi t 4-21: (P10/P11) NAC Circu it Wirin g – Class B
POWER-LIMITED
AND SUPERVISED
TYPICAL NOTIFICATION
APPLIANCE
P10 OR P11
SHIELD WIRE
INSULATE SHIELD WIRE
DO NOT LAND AT PANEL
CLASS A RETURN
Exhibi t 4-22: (P10/P11) NAC Circ uit Wiri ng – Class A