background image

FK-400-000  6 I56-3883-003

MODES OF OPERATION

INITIALIZATION

(Refer to the Configuration section below for further instructions). Once con-
figuration has started, the device performs an automatic initialization. This 
initialization sets the air flow baseline, the filter clogged baseline and the par-
ticulate level baseline. It is important that the system is connected properly 
and the filter is installed correctly when the device is initialized. These initial 
readings are used as a reference baseline to indicate when a fault occurs. In-
nitialization may take up to five minutes to complete.

STARTUP

Once powered, the FAAST system initializes using its stored configuration. 
The device checks and establishes its initial airflow, filter and fan settings. 
If all measurements are normal it begins normal operation. If any fault is de-
tected the appropriate fault LED will illuminate.

CONFIGURATION

The FAAST system is configured with FACP. The device receives the configura-
tion and performs a validation before the configuration becomes active. After 
validation of the data, the device performs an initialization with the new con-
figuration.

Failure of Configuration Validation

If configuration validation fails, the software configuration tool indicates a 
failure and the FAAST system illuminates the amber CONFIGURATION fault 
LED on the user interface. The device will not accept any of the data as valid. 
If a configuration fault occurs during the initial configuration or the device is 
unable to operate due to the configuration, the device must be re-configured 
by the FACP. If the configuration fault occurs after the initial configuration has 
been accepted, a Minor Fault relay will be set and the device reverts back to 
its last valid configuration.

Power or Network Loss during Configuration of E-mail

During an upload of configuration data, the FAAST system keeps the last 
known valid configuration in memory until a complete validation is com-
pleted on the new configuration data. This prevents data corruption in the 
event of a power loss or network failure. When power is restored the device 
performs a Startup with the last valid configuration. The device also indicates 
a CONFIGURATION fault on the user interface. This occurs only once. When 
the next Reset or Power On Reset is performed the device continues to use the 
last valid configuration.

NORMAL MODE

In Normal operating mode the FAAST system displays the air flow and current 
particulate levels on the user interface. The particulate level is compared to 
the threshold levels programmed into the device and activates the appropriate 
alarm as particulate levels exceed that threshold. If any fault occurs it acti-
vates the corresponding fault LED and relay.

TEST MODE

Test mode is initiated through the FACP or by depressing the TEST button on 
the user interface, when the button is enabled (refer to passcode access sec-
tion for activation details). 

ACCLIMATE

The FAAST system includes an available Acclimate mode. By allowing the de-
vice to operate in Acclimate mode, a device’s susceptibility to nuisance alarms 
can be reduced. This provides maximum protection for a device located in 
changing environments. The sensitivity of the unit continuously adjusts over 
time, within the set limits as the local environment changes. Acclimate mode 
must be activated and configured with the FACP. In Acclimate mode the de-

vice automatically adjusts the alarm point between a specified minimum and 
maximum sensitivity, programmed by the user. For the first 24 hours of opera-
tion the device monitors its environment. After the initial 24 hour period, the 
device adjusts the alarm point based on the particulate levels over a rolling 
1 hour period. It then adjusts the alarm level starting from the insensitive 
boundary, based on the stability of the environment being monitored. 

Setting Acclimate mode

The user chooses the boundaries for each alarm level in the Acclimate mode.  
The FAAST system  starts from the insensitive boundary and adjusts itself to 
stay within the sensitive boundary. 

ISOLATION

Isolation mode is initiated by pressing and releasing the ISOLATE button on 
the user interface when the button is enabled (refer to the passcode section) 
or placing the device into MODE 6 from the panel. When the ISOLATE button 
is activated or the command is issued, the isolation fault indicator illuminates 
on the user interface. In this mode the device operates normally but will not 
activate relays for any alarm or fault levels . Fire and fault events can still be 
seen on the user interface and the web server will send e-mail notification 
of events if enabled. Isolation mode will be held through resets and power 
outages. The device will remain in isolation mode until the isolation mode is 
removed by pressing the ISOLATE button or removing MODE 6 at the panel. 

DISABLE

Disable mode is initiated by pressing and holding the ISOLATE button on the 
user interface for 3 seconds when the button is enabled (refer to the passcode 
section) or issuing a disable command from the panel. When the ISOLATE 
button is activated or the 

disable

 command is issued, the isolation fault indi-

cator illuminates on the user interface. In this mode the fan switches off and 
the device does not report any alarm or fault levels on the user interface. This 
mode should only be used when the system needs to be taken offline. This 
mode will be held through resets and power outages. The device will remain 
in disable mode until the disable mode is removed by pressing 

and holding

 

the ISOLATE 

button for three seconds

 or the disable mode is removed at the 

panel.

USER BUTTON ALTERNATE FUNCTIONS
Passcode Access

The user interface has an option that requires users to enter a security code 
before the front panel functions become active. All passcodes must be 4 digits 
in length using numbers 1 through 9 (zero cannot be used). Passcodes may 
only be changed through the device specific page. In addition, the configura-
tion software tool is capable of locking out buttons individually, so that cer-
tain buttons may be accessed without a passcode, if desired.

The default passcode is ‘1111’.

The TEST button enters digits, the MODE button is used to enter the unlock 
mode and the ISOLATE button increments the current digit.

ALARM LEVEL

DEFAULT THRESHOLD  

%OBS/FT.

PROGRAMMABLE RANGE 

%OBS/FT.

DEFAULT THRESHOLD 

%OBS/M

PROGRAMMABLE 

RANGE %OBS/M

Alert

0.012

0.00046-400

0.0396

0.0015-13.0

Action 1

0.050

0.00046-400

0.165

0.0015-13.0

Action 2

0.100

0.00046-400

0.33

0.0015-13.0

Fire 1

0.250

0.00046-400

0.825

0.0015-13.0

Fire 2

0.500

0.00046-400

1.65

0.0015-13.0

TABLE 3. ALARM LEVEL PROGRAMMABLE RANGES

NOTE: Installation must be accomplished in accordance with all local codes and regulations. 
Product is UL certified to UL268. The 68-140 FAAST is UL approved from 0.00046 %/ft obs. to 4.0%/ft obs.  Evacuation via FACP (fire alarm control panel) 
must not be set higher than 0.743 %/ft obs. Product UL approved sensitivity range for D(l) classification is from 0.5 to 0.61 %/ft obs. from 300 to 4000 FPM.

FIGURE 9. PASSCODE ACCESS BUTTONS

ASP11-01

Summary of Contents for 68-140

Page 1: ...Aspiration Sensing Technology INSTALLATION AND MAINTENANCE INSTRUCTIONS TABLE OF CONTENTS INTRODUCTION SCOPE OF THIS MANUAL 2 DESCRIPTION FEATURES 2 ITEMS INCLUDED WITH UNIT 2 INSTALLATION PIPE INSTAL...

Page 2: ...n for increased filter life Electronic filter life monitoring Ultrasonic air flow sensing Field service access door Easy access filter maintenance door Event service and trend logs Pipe modeling softw...

Page 3: ...e circumstances when it may be necessary to connect a pipe to the exhaust port to divert the exhaust away from the location of the unit The output ports are tapered the same as the input ports to prov...

Page 4: ...the unit Refer to Table 1 for the proper electrical connections to the unit Refer to Table 2 for a typical connection for monitoring the FAAST system at a Fire Alarm Control Panel FACP SYSTEM POWERING...

Page 5: ...the current air flow is to either of these thresholds During normal operation two adjacent indicators are green and correspond to the current air flow entering the detector When airflow is at a balan...

Page 6: ...een a specified minimum and maximum sensitivity programmed by the user For the first 24 hours of opera tion the device monitors its environment After the initial 24 hour period the device adjusts the...

Page 7: ...r by illuminating the par ticulate bar graph to the appropriate number of segments for each digit as shown in Figure 11 The example shown in Figure 11 shows that the 5th number of the IP address is 6...

Page 8: ...ystem is equipped with internal memory that can be configured to log detector events Up to 18 000 events can be stored Events that are tracked include alarms faults and user actions Event tracking dat...

Page 9: ...dically thereafter Testing methods must statisfy the authority having jurisdiction Systems of fer maximum performance when tested and maintained in compliance with NFPA 72 and or CAN ULC S536 dependin...

Page 10: ...n number send defective units postage prepaid to System Sensor Returns WARRANTY Department RA __________ 3825 Ohio Avenue St Charles IL 60174 Please include a note describing the malfunction and suspe...

Reviews: