FK-400-000  9 I56-3883-003

FIGURE 14. BOTTOM VIEW OF UNIT

Wiring
Access

Plugs

Sampled

Air Inlet

Sampled

Air Outlet

Network

Connection

ASP-03

WEB SERVER

The FAAST system contains an integrated Web server which is used to ob-
serve detector configuration and may be used to remotely monitor the unit.

The Web server features include:

•  Intuitive interface for remote monitoring of faults, relays, particulate 

level, air flow, and power supply

•  Facility location and contact information

•  Configuration settings display
•  Event log viewer

E-MAIL NOTIFICATION

The FAAST system has the ability to send e-mail notifications to an individual 
or organization. Up to 6 different email addresses may be stored for notifica-
tion. Each email address can be configured to be notified of a specific alarm 
level, fault level or isolate condition through the PipeIQ software. E-mails from 
the device indicate a device’s ID, location and alarm or fault type. A com-
prehensive networking guide may be downloaded at systemsensor.com/faast.

CANNED SMOKE TESTING

All FAAST systems must be tested after installation and periodically thereafter. 
Testing methods must statisfy the authority having jurisdiction. Systems of-
fer maximum performance when tested and maintained in compliance with 
NFPA 72 and/or CAN/ULC S536 depending upon your national regulations.. 
UL Tested and approved aerosol smoke products are listed in Table 6.

MAINTENANCE

The only periodic maintenance required is to replace the filter assembly when 
the filter light is illuminated. Perform the following procedure to replace the 
filter assembly.

1.  Remove power from the system.
2.   Open the door on the right side of the device that covers the LED system 

indicators.

3.  Remove the plastic name card over the LEDs.
4.  Remove the two screws holding the filter assembly into the device.
5.  Remove the filter assembly and replace it with a new assembly.
6.   Torque the two philips head screws to 6in-lb (0.7 N-M) or 

¼

 turn past 

“lightly snug.” PLEASE DO NOT OVERTIGHTEN.

7.  Replace the plastic name card over the LEDs.
8.  Close the door and return power to the system.

Other system checks may need to be performed in accordance with local or 
national codes and regulations.

UL 

LISTED

COMPANY

AEROSOL 

ULC 

LISTED

COMPANY AEROSOL

Home 

Safeguard

25S

Home 

Safeguard

25S

SDI LLC

CHEK02, 

CHEK06

No Climb

SOLOA4

SOLOA3

SMOKE 

SABRE-01

SMOKE 

SABRE-01

TABLE 6. CANNED SMOKE TESTING

Summary of Contents for 68-140

Page 1: ...Aspiration Sensing Technology INSTALLATION AND MAINTENANCE INSTRUCTIONS TABLE OF CONTENTS INTRODUCTION SCOPE OF THIS MANUAL 2 DESCRIPTION FEATURES 2 ITEMS INCLUDED WITH UNIT 2 INSTALLATION PIPE INSTAL...

Page 2: ...n for increased filter life Electronic filter life monitoring Ultrasonic air flow sensing Field service access door Easy access filter maintenance door Event service and trend logs Pipe modeling softw...

Page 3: ...e circumstances when it may be necessary to connect a pipe to the exhaust port to divert the exhaust away from the location of the unit The output ports are tapered the same as the input ports to prov...

Page 4: ...the unit Refer to Table 1 for the proper electrical connections to the unit Refer to Table 2 for a typical connection for monitoring the FAAST system at a Fire Alarm Control Panel FACP SYSTEM POWERING...

Page 5: ...the current air flow is to either of these thresholds During normal operation two adjacent indicators are green and correspond to the current air flow entering the detector When airflow is at a balan...

Page 6: ...een a specified minimum and maximum sensitivity programmed by the user For the first 24 hours of opera tion the device monitors its environment After the initial 24 hour period the device adjusts the...

Page 7: ...r by illuminating the par ticulate bar graph to the appropriate number of segments for each digit as shown in Figure 11 The example shown in Figure 11 shows that the 5th number of the IP address is 6...

Page 8: ...ystem is equipped with internal memory that can be configured to log detector events Up to 18 000 events can be stored Events that are tracked include alarms faults and user actions Event tracking dat...

Page 9: ...dically thereafter Testing methods must statisfy the authority having jurisdiction Systems of fer maximum performance when tested and maintained in compliance with NFPA 72 and or CAN ULC S536 dependin...

Page 10: ...n number send defective units postage prepaid to System Sensor Returns WARRANTY Department RA __________ 3825 Ohio Avenue St Charles IL 60174 Please include a note describing the malfunction and suspe...

Reviews: