6.0 SYSTEM MAINTENANCE
6-12
CyberCat 254/1016 Operation Manual
UL S2203
Rev 6, 09/2015
P/N: 06-326-2
FM
6.4.2.4
DEVICE CONFIGURATION READ
This menu provides a means to read the configuration of all addressable devices connected to the panel.
From the Maintenance Menu 2, press the F4 button to access the screen:
1 2 3 4 5 6 7 8 9 0 1 2 3 4 5 6 7 8 9 0
A
R E A D A L L D E V I C E S
B
O N L O O P S : 1 2 3 4
C
P R E S S E N T E R T O S T A R T
D
D E V I C E S T O R E A D : N N N N
Exhibit 6-21: Configuration Read Screen
•
Row B -
Use the ◄►arrow buttons to move the cursor under the loop number; then use the +/-
buttons to select or deselect the loop for reading. Press ENTER to start the “Reading” process.
•
Row D – ‘NNNN’ shows the total number of devices the panel will read. This number will
decrement each time a device has been read.
For systems with a large number of devices to be read, the screen will return to the ‘System Normal’ display
after a few minutes of inactivity. The ‘System Normal’ display will indicate the current status of the
configuration read until completed.
1 2 3 4 5 6 7 8 9 0 1 2 3 4 5 6 7 8 9 0
A
C Y B E R C A T V 7 . X X
B
* R E A D I N G D E V : 1 - 0 0 2 *
C
D E V R E M A I N I N G : 0 0 0 9
D
A L : 0 0 0 S U : 0 0 0 T R : 0 0 0
Exhibit 6-22: System Normal Screen with Configuration Read Active
•
Row B – Displays the loop and address of the device currently being read.
•
Row C – Displays the number of device remaining to be read.
Once all devices have been read, the ‘System Normal’ screen will be displayed.