1.0 INTRODUCTION
1-8
CyberCat 254/1016 Operation Manual
UL S2203
Rev 6, 09/2015
P/N: 06-326-2
FM
Exhibit 1-6: Programming Features Cont.
Circuit or
Component
Program Feature or Option
Permitted
in UL
864?
(Y/N)
Possible Settings
(Defaults shown bold)
Settings
permitted
in UL 864
Notes
Network
Network Settings
Network Address (Panel ID)
Y
1
- 128
Network Module Type
Y
None
/ First / Middle / Last
1
Network Panel Message
Y
20 character user defined
(CUSTOM MSG PANEL 001)
where ZZZ = zone number
Network Switch Operation
Y
Global
/ Local
2
Network Switch IDs
Y
1 – 128
Selects which network
devices the panel will receive
switch commands from.
Network Zones
Y
1 – 254
3
Panel Supervision
Y
1 – 128
4
Wiring Style
Y
Style 4
/ Style 7
History
Y
Single
/ Multiple
Ethernet Settings
Source IP Address
Y
000.000.000.000
User Defined
5
Destination IP Address
Y
000.000.000.000
User Defined
6
Supervision IP Address
Y
000.000.000.000
User Defined
7
Panel IP Supervision
Y
000.000.000.000
4
History Transmits
Y
1
– 10
(Fike recommends 2)
Supervision Timeout
Y
1 – 59 (Sec., Min., Hour)
4 min. default
IP Time
Y
IP Time Disabled
Accept IP Time
Send IP Time
8
Notes:
1.
Defines the location of the panel with respect to others on the network.
2.
Defines if the respective panel will react to Reset, Silence, Acknowledge, and Drill commands received from other networked
panels.
3.
Defines which network zones will participate in the local panel zone(s).
4.
Defines which network panel(s) the selected panel should supervise.
5.
Defines the unique Internet Protocol (IP) address for the selected panel.
6.
Defines the unique Internet Protocol (IP) address for the panel that is to receive history events from the selected panel.
7.
Defines the unique Internet Protocol (IP) address for the panel that is to supervision responses from the selected panel.
8.
Used to synchronize panel time over the network.