1.0 INTRODUCTION
1-10
CyberCat 254/1016 Operation Manual
UL S2203
Rev 6, 09/2015
P/N: 06-326-2
FM
Exhibit 1-8: Programming Features Cont.
Circuit or
Component
Program Feature or Option
Permitted
in UL
864?
(Y/N)
Possible Settings
(Defaults shown bold)
Settings
permitted
in UL 864
Notes
Defaults
(Photo
Detector)
Remote Annunciator
Annunciator Type
Y
None
/ Remote LED –
Follows Red / Remote LED –
Follows Green / Remote LED
– Follows Amber / Remote
LED – Independent /
Sounder Base / Relay Base
1,2
Silenceable
Y
Silenceable /
Non- Silence
2
Positive Alarm Sequence (PAS)
Y
Disabled
/ Enabled
2
Output Settings – Priority Row
Y
1 – 8
1
Activation State
Y
No State
/ Alarm / Summing
Alarm / Test Alarm / Alarm
Verification ON / Pre-Alarm 1
/ Pre-Alarm 2 / Supervisory /
Trouble / Open Circuit
Trouble / Short Circuit
Trouble / Low Power Trouble
/ Maintenance Trouble /
Process / Zone Disable
Switch / Voice Alert / Voice
Evacuate / Voice Page /
Voice Play Message ID
Action Type
Y
No Action
/ Activate on
Any of 3 zones / Activate
on All of 3 zones / Activate
on Specific Device /
Activate on multiple
priority rows active
Output Pattern
Y
OFF
/ ON Continuous /
Slow / Fast / Temporal /
Walktest / Alert / Action
State Counter
Y
1
– 16
Notes:
1.
If annunciator type is set to Independent Operation, Sounder Base, or Relay Base an 8-row priority table will be displayed.
Table values are set using the Output Settings fields.
2.
If annunciator type is set to Sounder Base, Silence and Positive Alarm Sequence (PAS) options will be displayed.
Summary of Contents for CyberCat 1016