1.0 INTRODUCTION
UL S2203
CyberCat 254/1016 Operation Manual
1-17
FM
P/N: 06-326-2
Rev 6, 09/2015
Exhibit 1-15: Programming Features Cont.
Circuit or
Component
Program Feature or Option
Permitted
in UL
864?
(Y/N)
Possible Settings
(Defaults shown bold)
Settings
permitted
in UL 864
Notes
Defaults
(Supervised
Control
Module)
Common
Loop Number of Device
Y
1
- 4
1
Address of Device
Y
1
– 254
Output
Y
Enabled
/Disabled
Custom Message
Y
60 character user defined
(1-001 OUTPUT MODULE
Loop 1 - Address 001)
Custom Message
Y
Default/
User Defined
Zone Assignments
(device troubles)
Y
1
– 254
2
Defaults for Pre-Action
Y
Yes/
No
3
Defaults for 2 Stage Alarm
N
Yes/
No
4
Drill Output Pattern
Y
Drill Disabled /
On
Continuous
/ Slow / Fast /
Temporal
Output Silenceable
Y
Silenceable
/Non-Silenceable
Positive Alarm Sequencing
(PAS)
Y
Disabled
/ Enabled
Power Supply Monitor
Y
Enabled
/ Disabled
Output Control
Activation State
Y
Alarm
/ Summing Alarm /
Test Alarm / Alarm
Verification ON / Pre-Alarm 1
/ Pre-Alarm 2 / Supervisory /
Trouble / Open Circuit
Trouble / Short Circuit
Trouble / Low Power Trouble
/ Maintenance Trouble /
Process / Zone Disable
Switch / Voice Alert / Voice
Evacuate / Voice Page /
Voice Play Message ID /
MNS Message Active
Action Type
Y
No Action /
Activate on Any
of 3 zones
/ Activate on All of
3 zones / Activate on Specific
Device / Activate on multiple
priority rows active
Output Pattern
Y
OFF /
ON Continuous
/ Slow
/ Fast / Temporal / Walktest /
Times / Custom Defined
Output Pattern Set
Y
1
- 3
State Counter
Y
1
– 16
Zone Assignments (activation)
Y
1
- 255
5
Notes:
1.
CyberCat 254 has only one (1) addressable loop. CyberCat 1016 can have up to four (4) addressable loops.
2.
Can be assigned to 4 discrete zones, 2 zone ranges or 1 range and 2 discrete zones.
3.
Modifies control module configuration for use with Pre-Action solenoid.
4.
If selected, the control module configuration will be modified for 2-Stage Alarm Operation (City of Chicago).
5.
Can be assigned to any 3 zones, 254 any zone, or 255 any zone (non-disable).