1.0 INTRODUCTION
1-22
CyberCat 254/1016 Operation Manual
UL S2203
Rev 6, 09/2015
P/N: 06-326-2
FM
Exhibit 1-20: Programming Features Cont.
Circuit or
Component
Program Feature or Option
Permitted
in UL
864?
(Y/N)
Possible Settings
(Defaults shown bold)
Settings
permitted
in UL 864
Notes
Defaults
(Conv. Zone
Monitor
Module)
Loop Number of Device
Y
1
- 4
1
Address of Device
Y
1
– 254
Custom Message
Y
60 character user defined
(1-001 CONV ZONE MOD
Loop 1 - Address 001)
Custom Message
Y
Default /
User Defined
Zone Assignments
Y
1
– 254
2
Input Function
Y
No Input Function
/
Detection
/ Pre-Alarm 1 /
Pre-Alarm 2 / Supervisory
Wire Class
Y
Class B
/ Class A
IDC Power Off Time (seconds)
Y
4 – 64
(8 sec. default)
(4 sec
increments)
Alarm Verification
Y
Disabled
/ Enabled
Y
Time: 0 – 60 seconds
Defaults
(Update
Device
Checksum)
Recalculate addressable device
Configuration Checksums?
Y
Yes / No
Defaults
(Reset
Default
Config.)
Reset All Default Device
Configurations?
Y
Yes / No
Defaults
(Custom
Messages
Panel LCD Custom Message
Line 2 Logo
Y
20 character user defined
(
Fike Corporation
)
Addressable Devices
(Restores all device custom
messages to default)
Y
Yes / No
Peripheral Devices
(Restores all device custom
messages to default)
Y
Yes / No
Air Sampling Devices
(Restores all device custom
messages to default)
Y
Yes / No
Defaults
(Password)
Used to assign a unique Level 2
password (8 available)
Y
4 digit user defined
Notes:
1.
CyberCat 254 has only one (1) addressable loop. CyberCat 1016 can have up to four (4) addressable loops.
2.
Can be assigned to 4 discrete zones, 2 zone ranges or 1 range and 2 discrete zones.
Summary of Contents for CyberCat 1016
Page 135: ......