1.0 INTRODUCTION
1-28
CyberCat 254/1016 Operation Manual
UL S2203
Rev 6, 09/2015
P/N: 06-326-2
FM
Exhibit 1-26: Programming Features Cont.
Circuit or
Component
Program Feature or Option
Permitted
in UL
864?
(Y/N)
Possible Settings
(Defaults shown bold)
Settings
permitted
in UL 864
Notes
LED
Annunciator
20-Zone
Assignment by LED
Select LED Assignments
Y
1 - 40
Relay
Controller
Peripheral Address
Y
2 - 32
Local Buzzer
Y
Enabled
/ Disabled
Relay Group Configuration (1 – 6)
Relay
Y
1 - 4
Function
Y
No Function Assigned
/ On
– Device Activation / On –
Device Trouble / On – Device
PreAlarm / On – Zone
Process / On – Zone Trouble
/ On – Zone Supervisory / On
– Zone Abort / On – Zone
Disabled / On – Zone
PreAlarm / On – Zone Alarm /
On – Zone PreDischarge / On
– Zone Release / On - Zone
Test Alarm / On – Zone
Action / On – Any Network
Device / On – Any Network
Device Trouble / On – Any
Network Device PreAlm / Off
– Any Network Device / Off –
All Network Device
1
Assignment by Device
Select Devices
Y
1 – 254
Selection Options
Y
Select
/ Clear
Y
All Addresses
/ Even
Addresses / Odd Addresses /
All Photo Sensors / All
Photo/Heat Sensors / All
Photo/Duct Sensors / All Ion
Sensors / All Heat Sensors / All
Monitor Modules / All Dual
Monitor Modules / All Mini
Monitor Modules / All Pull
Station Modules / All
Conventional Zone / All Control
Modules / All Relay Modules /
All Releasing Modules / All
FAAST Sensors
Y
On Loop:
1
– 4
Y
Between:
1
– 254
Y
And: 1 –
254
Y
Select All / Clear All / Invert
All
Summary of Contents for CyberCat 1016
Page 135: ......