1.0 INTRODUCTION
1-32
CyberCat 254/1016 Operation Manual
UL S2203
Rev 6, 09/2015
P/N: 06-326-2
FM
Exhibit 1-30: Programming Features Cont.
Circuit or
Component
Program Feature or Option
Permitted
in UL
864?
(Y/N)
Possible Settings
(Defaults shown bold)
Settings
permitted
in UL 864
Notes
Smoke
Control
Graphic Card
6-Zone
Smoke Group Configuration
Group
Y
1
- 6
Switch Group Configuration
Y
On / Off / Auto
Switch Function
Y
No Function Assigned
/
Smoke Control
Select Relay Actions
(when switch is pressed)
Y
None
/ On / Auto / Off
1,2
Action Start
Y
Action starts with
confirmation address OR
delay timer / Action starts
with confirmation address
AND delay timer
Confirmation Address
Y
Loop:
0
– 4
Address:
0
- 254
Relay Address
Y
Panel:
0
- 128
Loop:
0
- 4
Address:
0
- 254
Delay (relay activation)
Y
0
– 255 seconds
Delay Timer Start
Y
Delay timer starts
immediately / Delay timer
starts after confirmation
address activates
LED Configuration
Y
On / Off / Auto / Fault
Notes:
1.
On and Off overrides up to 25 addressable relays on the panel’s SLCs.
2.
Auto returns up to 25 addressable relays back to automatic configured state.
Summary of Contents for CyberCat 1016
Page 135: ......