1.0 INTRODUCTION
UL S2203
CyberCat 254/1016 Operation Manual
1-35
FM
P/N: 06-326-2
Rev 6, 09/2015
Exhibit 1-33: Programming Features Cont.
Circuit or
Component
Program Feature or Option
Permitted
in UL
864?
(Y/N)
Possible Settings
(Defaults shown bold)
Settings
permitted
in UL 864
Notes
Voice EVAC
Amplifier
Common
Application Type
Y
Single Channel
/ Dual
Channel / Page Only
1
Miscellaneous
Peripheral Address
Y
2 - 32
Locality
Y
Standard
/ Boston / Chicago
/ NYC
Standard
2
Record and Repeat Tones
Y
Play Tones
/ No Tones
Play
Tones
3
Periodic Tones For Fire Page
When Not Speaking
Y
Play Tones /
No Tones
6
Periodic Tones For MNS Page
When Not Speaking
N
Play Tones
/ No Tones
Play
Tones
7
Speaker Voltage Output
Y
25 VAC /
70.7 VAC
Power Input
Y
120 VAC
/ 240 VAC
Audio Bus
Y
Enabled
/ Disabled
Local Microphone
Y
Enabled /
Disabled
Battery Charger
Y
Enabled
/ Disabled
Local Piezo
Y
Enabled
/ Disabled
NAC
State
Y
Alarm
/ Pre Alarm 2 / Pre
Alarm 1 / Supervisory /
Trouble / Process
Synchronization
Y
None
/ Gentex / System
Sensor
Zones
Y
1 – 254
4
Silenceable
Y
Silence
/ Non-Silence
Drill
Y
Enabled
/ Disabled
Walk Test
Y
Enabled
/ Disabled
Active During Fire Playback
Y
Enabled /
Disabled
5
Active During Fire Page
Y
Enabled /
Disabled
5
Active During MNS Playback
Y
Enabled /
Disabled
5
Active During MNS Page
Y
Enabled /
Disabled
5
NAC Delay Timeout
Y
0
– 250 seconds
Strobe OFF after Silence
Y
Enabled /
Disabled
Contact Monitor
Contact
Y
Disabled
/ Enabled
Message 1
Y
Select ID number (1 – 16)
Message 2
Y
Select ID number (1 – 16)
Notes:
1.
Select the type of application that the amplifier is being utilized as.
2.
Locality setting is configured for operation of local jurisdiction requirements for only Boston, Chicago and New York. Outside of these jurisdiction
then the setting should be set to Standard
3.
Allows the selection to play MNS tone and Fire tones between record and repeat messages.
4.
Select the zone number(s) that will activate the NAC.
5.
These need to be enabled when you want the NAC circuit on the Amplifier to activate off of an event.
6.
Allows the selection to play Fire tones periodically when no live announcement is made during Fire page.
7.
Allows the selection to play MNS tones periodically when no live announcement is made during MNS page.