1.0 INTRODUCTION
UL S2203
CyberCat 254/1016 Operation Manual
1-39
FM
P/N: 06-326-2
Rev 6, 09/2015
Exhibit 1-37: Programming Features Cont.
Circuit or
Component
Program Feature or Option
Permitted
in UL
864?
(Y/N)
Possible Settings
(Defaults shown bold)
Settings
permitted
in UL 864
Notes
Switch Card
20-Zone
Peripheral Address
Y
2 - 32
Switch Configuration (1 – 20)
Function
Y
No Function Assigned
/
Panel Reset / Panel Silence /
Panel Acknowledge / LED
Test / Panel Walktest Mode 1
/ Panel Walktest Mode 2 /
Panel Drill / Zone Process
Toggle / Zone Disable Toggle
/ Smoke Control / Alarm
Silence / Supervisory Silence
/ Trouble Silence / Alarm
Signal Cancel / Voice Alert /
Voice Evacuate / Voice Page
/ Voice Record Page / Voice
Page to Alert / Voice Page to
EVAC / Voice Play Message
ID / MNS Silence / MNS
Page / MNS Record Page /
MNS Play Message ID / AHU
Restart
Zone
Y
0
– 254
2,3
Settings
Y
Relay Action Settings / Zone
Assignments / Zone and
Message ID
4
Y
Latching
/ Non-Latching
Latching
5
Priority
Y
0 – 254
(Default 1)
1
Switch Timeout
Y
0
– 250 (min.)
0
5
Message ID1
Y
1 - 16
6
Message ID2
Y
1 - 16
6
Notes:
1.
0 = None; 1 = Highest and 254 = Lowest.
2.
This field is active for Zone Process and Zone Disable Toggle functions only.
3.
Selects zone number to be associated with switch activation.
4.
This field is active only when the function is set for Smoke Control, Voice Alert, Evacuate, Page, Record Page or Voice Play
Message ID.
5.
This is only allowed on MNS switch functions
6.
This field is used only when the switch function is assigned to Play Message ID.