2.0 USER INTERFACE
2-2
CyberCat 254/1016 Operation Manual
UL S2203
Rev 6, 09/2015
P/N: 06-326-2
FM
2.1.1
SYSTEM STATUS LEDs
Exhibit 2-2: Status LEDs
Exhibit 2-3: Status LED Descriptions
Indicator
Color
When Active
To Turn Off
AC Power
Green
Illuminates steady when proper primary AC
power is applied. Normally ON.
Turns off when AC power is removed or is
too low for proper operation.
Alarm
Red
Flashes when the panel enters the Alarm
State. Illuminates steady after you
Acknowledge or Silence the event.
Clear the Alarm condition and reset the
system.
Trouble
Yellow
Flashes when the panel enters the Trouble
State or if a zone or device is disabled.
Illuminates steady after you Acknowledge or
Silence the event.
Clear the Trouble condition.
Some trouble
events are latching. If latching, the panel
must be reset to restore the system to
normal.
Supervisory
Yellow
Flashes when the panel enters the Supervisory
State or if a zone or device is disabled.
Illuminates steady after you Acknowledge or
Silence the event.
Clear the Supervisory condition.
(Supervisory inputs may be configured as
latching or non-latching. If configured for
latching, the panel must be reset to restore
the system to normal.)
Silence
Yellow
Illuminates steady after you Silence the event,
either locally at the main display or remotely at
a remote display unit. Silencing the system
turns off the panel’s integral audible and all
notification appliance circuits that are
programmed as Silenceable.
Turns off when the panel is reset or another
system event occurs. NFPA 72 requires
that a silenced panel resound every 24
hours.
Pre-Alarm 1
Red
Flashes when the panel enters the Pre-Alarm 1
State. Illuminates steady after you
Acknowledge or Silence the event.
Turns off when the Pre-Alarm 1 goes below
the set level or the panel is reset.
Pre-Alarm 2
Red
Flashes when the panel enters the Pre-Alarm 2
State. Illuminates steady after you
Acknowledge or Silence the event.
Turns off when the Pre-Alarm 2 goes below
the set level or the panel is reset.
Disabled
Yellow
Illuminates steady when any device or zone is
disabled. Outputs in the disabled zone will not
operate. Panel will also indicate a Supervisory
and Trouble event when a zone is disabled.
Turns off when panel is reset or a device or
circuit is enabled.
Walk-Test
Yellow
Flashes when the panel is placed into Walk-
Test State. Illuminates steady after you
Acknowledge or Silence the event.
Turns off if the Walk-Test condition clears or
if the panel is reset.
Ground Fault
Yellow
Illuminates steady when a system Ground
Fault condition is present on the system.
Turns off when the ground fault is cleared or
the panel is reset.
Summary of Contents for CyberCat 1016
Page 135: ......