5.0 SYSTEM DIAGNOSTICS
UL S2203
CyberCat 254/1016 Operation Manual
5-9
FM
P/N: 06-326-2
Rev 6, 09/2015
5.5.3
VESDA 2 DIAGNOSTICS
The VESDA 2 Diagnostics screen allows you to view the current fault list for the selected VESDA unit. From
Diagnostic Menu 2 screen, press the F3 button to view the VESDA 2 Diagnostic screen:
1 2 3 4 5 6 7 8 9 0 1 2 3 4 5 6 7 8 9 0
A
V E S D A Z O N E N U M : 0 0 1 >
B
E N T E R F O R F A U L T L I S T
C
- - - - - - - - - - - - - - -
D
- - - - - - - - - - - - - - -
Exhibit 5-12: VESDA 2 Diagnostics Screen
•
Row A -
Allows you to select the VESDA zone number to view. Use the ◄► arrow buttons to
position the cursor in ones, tens, or hundreds field; then press the +/– buttons to change the
value at cursor. Arrow (< >) moves back and forth to indicate communication with VESDA unit.
•
Row B - Press the ENTER button to list the active faults for the VESDA zone number displayed in
Row A.
•
Rows C & D - Displays the active faults.
5.5.4 PERIPHERAL DIAGNOSTICS
The Peripheral Diagnostics screen allows you to view the status of the communication between the CyberCat
controller and the devices connected to its peripheral bus. From the Diagnostic Menu 2 screen, press the F4
button to view the Peripheral Diagnostic screen:
1 2 3 4 5 6 7 8 9 0 1 2 3 4 5 6 7 8 9 0
A
A D R : 0 2 S U P : 0 0 M A X : 0 0
B
T Y P E :
B O S C H D A C T
C
C O M M A N D S S E N T : 0 0 0 0 0
D
C O M M A N D S R C V D : 0 0 0 0 0
Exhibit 5-13: Peripheral Diagnostics Screen
•
Row A (ADR) - Allows you to select the peripheral address to view. Use the +/- buttons to select
the Peripheral ID to diagnose.
•
Row A (SUP) - Displays the number of times the panel sent a supervision message without a
response.
•
Row A (MAX) - Counts the number of times a supervision message was sent without response
from peripheral. After a count of 12 times without a response, a peripheral trouble will occur.
•
Row B - Displays the TYPE of peripheral device configured at the selected peripheral address
shown in Row A (See device list below).
•
Row C - Displays the number of supervision commands sent to the peripheral device selected.
•
Row D - Displays the number of supervision commands received from the peripheral device
selected.
Available Peripheral Devices:
Rem Disp 14Key
Print+Gateway (MIM)*
Switch 20-Zone
Digital Paging
256 LED Graphic
Gateway Only (MIM)*
Annunc 20-Zone
Relay Control
Zone Graphic
Ethernet Port
Computer
Class A Module
Print Serial (MIM)
Rem Disp 10Key
Amplifier
Remote MIC
Bosch DACT
Rem Disp 2 Key
Fire-Phone Int
1
Print Parallel (MIM)
Smoke Control
6Z Voice EVAC
1
Press F1 to access advanced diagnostics
Press the F4 button to display the firmware version of the selected peripheral device on Rows C & D.
* Gateway Only and Print+Gateway is not available in Panel Firmware V7.00 and higher.