System Options
Programming
FCP-300/FCP-300ECS Manual —
P/N LS10145-002FK-E:A 3/12/2021
105
9.6 System Options
This Section of the manual explains how to customize software options that affect general operation of the System. This
includes such items as: Communication Options, Daytime/Nighttime Sensitivity, Holiday Days, Time Options, Miscellaneous
Options, Daylight Saving Options, Edit Banner, and SLC Family. Refer to each individual subsection for complete instruc-
tions.
9.6.1 Communication Options
Auto Test Time
To access the automatic communicator test time screen:
1.
Enter the Installer Code.
2.
Select 7 for the Program Menu.
3.
From the Program Menu, select 5 for the System Options.
4.
Press 1 for the Communication Options.
5.
Select 1 for the Auto Test Time.
6.
Enter the hour you want the control panel to send an Automatic Test Report (or press the up or down arrow), then press
ENTER.
7.
Enter the minutes (or press the up or down arrow), then press ENTER.
8.
Select AM or PM by pressing the up or down arrow, then press ENTER.
9.
Select the Report Time Interval by pressing the up or down arrow, then press ENTER. The Time Interval selections are
24hrs, 12hrs, 6hrs and 4 hrs.
NOTE:
The AM and PM are only available if the panel “Clock Options” are set for AMPM mode. Otherwise the clock is in military
time and AMPM is not selectable.
Phone Lines
To access the phone lines screen, do the following.
1.
Enter the Installer Code.
2.
Select 7 for the Program Menu.
3.
From the Program Menu, select 5 for the System Options.
4.
Select 1 for the Communication Opts.
5.
Select 2 for the Phone Lines Menu.
FIK-NVCM, FIK-RVM
UNUSED
Refer to the Comments column of
“Programming Options for FIK-
6815 Modules” on page 98 for the
description of these options.
Latch or Non-latching feature only
appears for the following:
-WATERFLOW,
-FIRE SUPERVISORY,
-FIRE TAMPER,
-ZONE AUX1, ZONE AUX2, -
System AUX1, System AUX2,
-ECS INPUT, ECS TAMPER, and
-ECS SUPERVISORY.
SWITCH
MANUAL PULL
WATERFLOW
FIRE SUPERVISORY
FIRE TAMPER
FIRE DRILL
SILENCE
RESET
P.A.S. ACK
ZONE AUX1
ZONE AUX2-
System AUX1
System AUX2
MANUAL RELEASE
INTERLOCK
STATUS POINT
VOICE AUX STATUS 1-2
VOICE AUX ECS 1-4
Background Music
ECS INPUT
User also has the ECS Event
Number 1-8 option for ECS INPUT.
Only available when an FIK-NVCM
is installed in the System to the
FIK-NVCM/FIK-RVM choice part.
ECS TAMPER
ECS SUPERVISORY
Choices
Type Selections
Function Selections for
each Type
Comments
Table 9.7 Point Programming Options for FIK-NVCM and FIK-RVM (Continued)