System Options
Programming
FCP-300/FCP-300ECS Manual —
P/N LS10145-002FK-E:A 3/12/2021
107
Line Monitor
Enable the line monitor for each phone line that will be used. See “Phone Lines Editing Screen” on page 106 for the location of
this field on the phone lines screen. When the phone line monitor has been enabled for a phone line, a trouble condition will
occur if the line is not connected. If a phone line will not be used, it must be disabled.
12. Select Y (monitor line) or N (don’t monitor line) by pressing the up or down arrow, then press ENTER.
Answering Machine Bypass
This option is used in conjunction with the HFSS Programming Tool. This feature ensures that an answering machine will not
interfere with the communication between the panel and the computer. If an answering machine is used at the panel site, enable
this feature; if an answering machine is not used, disable the feature.
This option is factory-programmed as Yes (enabled).
The selection made here must match the programming for this option in the Communication Configuration dialog box of the
HFSS.
13. Select Y (answering machine bypass enabled) or N (Answering Machine Bypass disabled) by pressing the up or down
arrow, then press ENTER.
Phone Line Unused
This option is used so that you can set the unused phones lines to “Yes”, so no auto-test will be sent through that line.
This option is factory programmed as No.
14. Select Y or N by pressing the up or down arrow key, then press ENTER.
Edit Ethernet
1.
Enter the Installer Code. The panel will automatically access the Main Menu.
2.
Select 7 for Panel Programming.
3.
Select 5 for System Options.
4.
From the next Menu, select 1 for Communication Opts.
5.
Select 3 for Edit Ethernet.
Figure 9.10 Edit Ethernet Message
AlarmNet Timers
1.
Enter the Installer Code. The panel will automatically access the Main Menu.
2.
Select 7 for Panel Programming.
3.
Select 5 for System Options.
4.
From the next Menu, select 1 for Communication Opts.
5.
Select 4 for AlarmNet Timers.
6.
The available options for AlarmNet Timers are as follows: *default
• Ethernet: None, 75 seconds, 90 seconds, 3 minutes, *5 minutes, 1 hour, 24 hours,30 days.
• Old Alarm: None, 10 minutes, 15 Minutes,*30 Minutes, 1 Hour, 2 Hours, 4 Hours, 6 Hours, 12 Hours, 24 Hours. (Sets
how long an undeliverable alarm is retried for delivery to the Central Station. If the message is not validated, it is retried
until the old alarm time is reached or the message is validated)
.
Figure 9.11 AlarmNet Timers
Phone Line Gains
1.
Enter the Installer Code. The panel will automatically access the Main Menu.
2.
Select 7 for Panel Programming.
3.
Select 5 for System Options.