9.6.4 Time Options
Through this programming option, you can set the water flow delay time, alarm verification time, AC report delay, AC-Fre-
quency, Auto-Resound, and Clock Format.
Water Flow Delay
You can program a delay of 0-90 seconds (zero means no delay) to be used in conjunction with a water flow switch. The delay
is System-wide. All water flow switches on the System will use the same delay period.
To access the screen for programming water flow delay, follow these steps:
1.
Enter the Installer Code.
2.
Select 7 for Program Menu.
3.
Select 5 for System Options.
4.
Select 4 for Time Options.
A screen similar to the one shown in “Water Flow Delay Programming Screen” on page 109 will display.
Figure 9.14 Water Flow Delay Programming Screen
5.
Enter the number of seconds (0 to 90) to delay an a water flow switch alarm, then press ENTER.
Alarm Verify
You can set the alarm verification time from 60 to 250 seconds (default is 60 seconds).
To set the alarm verification:
6.
Enter the desired number of seconds for the alarm verification time.
7.
Press the right arrow or ENTER to make your selection and move to the next Programming option.
AC Report Delay
NOTE:
You must select 1-3 hours in UL Central Station installations and UL remote signaling installations.
You can adjust the number of hours before a Low AC Report will be sent to the Central Station.
To program low AC report delay, follow these steps:
NOTE:
The Steps continued from step 7 of Section “Alarm Verify” on page 109.
8.
Enter the number of hours (0-30) before a low AC report will be sent to the Central Station, then press ENTER.
Change AC Line Frequency
The panel’s AC line frequency is selectable for 50, 60 Hz, or Internal. AC Frequency feature dictates how the control panel
will calculate time based on the AC line frequency used in the installation site. The “Internal” option can be used in areas
where the AC line frequency is not dependable and you want the panel to calculate time from the internal crystal. The internal
crystal is not as accurate as the AC power source and either 60 Hz or 50 Hz should normally be selected. The panel defaults to
the 60 Hz. selection
To change the AC line frequency, continue programming from step 9 above:
9.
Select 50, 60 or Intl, by pressing the up or down arrow, then press ENTER.
Clock Display Format (AM/PM or Military)
To change the System Clock display format, continue programming from step 8 above:
10. Select AMPM (for AM/Pm display format) or MIL (for military or 24 hr display format) by pressing the up or down
arrow, then press ENTER.
Auto-Resound (4 or 24 hours)
The System resound time period can be modified from the default value 24 hours to 4 hours. This setting adjusts when the
FACP will automatically resound events after being silenced. Set this option to 4 hours when using SWIFT devices.
9.6.5 Miscellaneous Options
Through this Programming option, you can turn on or turn off the Strobe Synchronization during the silence and the display
status at idle (auto display event).
To edit Miscellaneous Options, do the following.
1.
Enter the Installer Code.
2.
Select 7 for the Program Menu.
Delay in seconds before waterflow alarm
occurs (0-90)