124
FCP-300/FCP-300ECS Manual —
P/N LS10145-002FK-E:A 3/12/2021
System Operation
Smoke Alarm Verification
10.8 Smoke Alarm Verification
Figure 10.7 illustrates how the Smoke Alarm Verification cycle operates.
Figure 10.7 Smoke Verification Cycle
During the Confirmation Period if there is no alarm indication then the System will return to normal operation.
10.9 Function Keys
The function keys on the FCP-300/ECS have multiple features. Their macro key functionality can simplify the disabling, acti-
vating, or inhibiting points or groups respectively. They can also be used as a status type activation event and for activating
Map Inhibit. Each F-Key macro can hold 50 events.
To access the F-Key Recording menu:
1.
From the Idle screen, press and hold the F-Key for 5 seconds.
2.
Enter a PIN with F-Key macro recording privileges, if prompted.
10.9.1 Recording an F-Key Macro
1.
Access the F-Key Recording Menu and select the ‘Start FKEY Recording’ option.
2.
The panel will return to the Idle screen. Notice the 4th line on the display now alternates with <F# Key Recording>,
where # is the number of the F-Key being recorded.
3.
Any Disabling or Activating of points, output groups, or templates from the site at this point will be programmed into the
macro. Do this by going to any annunciator within the site and entering Main Menu -> Point Functions and use
Disable/Enable Point or use I/O Point Control to: disable output groups or individual points, or activate individual points.
4.
Once you are finished with disabling or activating points/output groups, enter the F-Key Recording Menu again and
select the ‘End FKEY Recording’ option.
5.
The panel will return to the Idle screen.
10.9.2 Aborting an F-Key Macro Recording Session
1.
After an F-Key macro recording session has been started, the session can be canceled at any time by accessing the F-Key
Recording Menu and selecting ‘Abort FKEY Recording’ option.
2.
The panel will return to the Idle screen.
10.9.3 Erasing an F-Key Macro
1.
If an F-Key macro has already been recorded, you can erase it by accessing the F-Key Recording menu and selecting the
‘Erase FKEY Macro’ option.
2.
The panel will return to the Idle screen.
10.9.4 Using a Recorded F-Key Macro
1.
From the Idle screen on any annunciator in the site, press the F-Key you want to activate.
2.
Once finished, to de-activate the macro press the F-Key again.
10.9.5 F-Key Status Event
When an F-Key is enabled, it activates its corresponding F-Key Active Event. This is a status type event that can activate out-
puts without showing any status on annunciator displays. This should be used for ancillary purposes only.
10.9.6 F-Key Map Inhibit
The F-Keys have the ability to disable event - output group mapping for the purpose of simulating that the map doesn’t exist.
This can be setup to allow for the testing purposes where the notification of an entire building is not desired during the test.
This option is programmable for each Output Group Map through HFSS Programming Tool.
When an F-Key is active and a map in the System is set to be disabled by the Map Inhibit, the System will show a trouble event
indicating it as such.