136
FCP-300/FCP-300ECS Manual —
P/N LS10145-002FK-E:A 3/12/2021
Section 12: Reporting
This Section lists the receivers that are compatible with this control panel, and the reporting codes sent by the control panel for the SIA
and Contact ID formats.
12.1 Receivers Compatible with the Control Panel
“Receivers Compatible with the Control Panel” on page 136 show the receivers compatible with the control panel. This table includes,
but it is not limited to the Central Stations listed below.
Manufacturer
Model
Format
Honeywell
Model 9800
SIA and Contact ID
Model 9000 (SIA formats)
SIA
Honeywell Security
AlarmNet 7810-ir
Contact ID only
Ademco
MX8000
SIA and Contact ID
Ademco
Model 685 (Contact ID )
Contact ID
Sur-Gard
SG-MLR2-DG (V. 1.64 or higher)
SIA and Contact ID
Osborne Hoffman
Quickalert
SIA and Contact ID
Table 12.1 Receivers Compatible with the Control Panel
SIA Reporting Format
Contact ID Reporting Format
SIA pi Modifier
SIA
Event Description
Module ID
# (If Any)
SIA
Event
Codes
Parameter
Fixed Length
Format NN - panel
ID
XX- SBUS ID
ZZZ- Zone #
PPPP- Point #
GGG- Group #
E- Emergency #
RRRR-Receiver #
Qualifier
Event
Code
Group #
Contact #
System Events
System Events are reported when either “Report by Point” or Report by Zone is selected
AC power low trouble
AT
0
ATNN000000
1
301
00
000
AC power low trouble restore
AR
0
ARNN000000
3
301
00
000
Auto dialer test communications trouble
line 1
YC
1
YCNN000001
1
350
Receiver # 001
Auto dialer test communications trouble
line 1 restore
YK
1
YKNN000001
3
350
Receiver # 001
Auto dialer test communications trouble
line 2
YC
2
YCNN000002
1
350
Receiver # 002
Auto dialer test communications trouble
line 2 restore
YK
2
YKNN000002
3
350
Receiver # 002
Automatic test normal
RP
0
RPNN000000
1
602
00
000
Automatic test off normal
RY
0
RYNN000000
1
608
00
000
Battery voltage trouble
YT
Exp. ID
YTNNXX0000
1
302
Exp. ID
000
Battery voltage trouble restore
YR
Exp. ID
YRNNXX0000
3
302
Exp. ID
000
Date changed event
JD
0
JDNN000000
1
625
00
000
ECS Reset
OR
1
ORNN000001
1
401
00
001
Emergency System Overridden
QS
0
QSNN000000
1
244
00
000
Emergency System Overridden Restore
QR
0
QRNN000000
3
244
00
000
Fire drill has begun
FI
0
FINN000000
1
604
00
000
Fire drill has ended
FK
0
FKNN000000
3
604
00
000
F1 Mapping Inhibited
FT
2001
FTNN002001
1
570
00
001
F1 Mapping Inhibited Restoral
FJ
2001
FJNN002001
3
570
00
001
F2 Mapping Inhibited
FT
2002
FTNN002002
1
570
00
002
F2 Mapping Inhibited Restoral
FJ
2002
FJNN002002
3
570
00
002
F3 Mapping Inhibited
FT
2003
FTNN002003
1
570
00
003
F3 Mapping Inhibited Restoral
FJ
2003
FJNN002003
3
570
00
003
F4 Mapping Inhibited
FT
2004
FTNN002004
1
570
00
004
F4 Mapping Inhibited Restoral
FJ
2004
FJNN002004
3
570
00
004
Fire Reset
OR
0
ORNN000000
1
401
00
000
Fire System Overridden
FS
0
FSNN000000
1
245
00
000
Fire System Override Restore
FR
0
FRNN000000
3
245
00
000
Ground fault condition trouble
YP
Exp. ID
YPNNXX0000
1
310
Exp. ID
000
Ground fault condition trouble
restore
YQ
Exp. ID
YQNNXX0000
3
310
Exp. ID
000
Table 12.2 Report Formats Table