138
FCP-300/FCP-300ECS Manual —
P/N LS10145-002FK-E:A 3/12/2021
Reporting
Receivers Compatible with the Control Panel
User initiated manual dialer test
RX
0
RXNN000000
1
601
00
000
Walk Test begin
TS
0
TSNN000000
1
607
00
000
Walk Test end
TE
0
TENN000000
3
607
00
000
Table 12.2 Zone Events
Note:
Zone events are reported only when “Report by Zone” is selected
Auxiliary power trouble
FT
0000
FTNN000000
1
320
00
000
Auxiliary power trouble restore
FJ
0000
FJNN000000
3
320
00
000
CO Detector Alarm
GA
Zone #
GANN000ZZZ
1
162
00
Zone #
CO Detector Alarm Restore
GH
Zone #
GHNN000ZZZ
3
162
00
Zone #
CO Detector Supervisory Alarm
GS
Zone #
GSNN000ZZZ
1
200
00
Zone #
CO Detector Supervisory Alarm Restore
GR
Zone #
GRNN000ZZZ
3
200
00
Zone #
CO Detector Trouble
GT
Zone #
GTNN000ZZZ
1
373
00
Zone #
CO Detector Trouble Restore
GJ
Zone #
GJNN000ZZZ
3
373
00
Zone #
Detector Alarm
FA
Zone #
FANN000ZZZ
1
110
00
Zone #
Detector Alarm Restore
FH
Zone #
FHNN000ZZZ
3
110
00
Zone #
Detector trouble
FT
Zone #
FTNN000ZZZ
1
373
00
Zone #
Detector trouble restore
FJ
Zone #
FJNN000ZZZ
3
373
00
Zone #
ECS Switch Trouble
QT
0
QTNN000000
1
242
00
000
ECS Switch Trouble Restore
QJ
0
QJNN000000
3
242
00
000
ECS Supervisory/Tamper Alarm
QS
0
QSNN000000
1
241
00
000
ECS Supervisory/Tamper Alarm
Restore
QR
0
QRNN000000
3
241
00
000
ECS Output Group Trouble
QT
Group # +1000
QTNN001GGG
1
320
00
Group #
ECS Output Group TroubleRestore
QJ
Group # +1000
QJNN001GGG
3
320
00
Group #
External Reset/Silence/Fire Drill switch
trouble
UT
0000
UTNN000000
1
373
00
000
External Reset/Silence/Fire Drill switch
trouble restore
UJ
0000
UJNN000000
3
373
00
000
LOC Mic Activated ECS Alarm
QA
0
QANN000000
1
220
00
000
LOC Mic Activated ECS Alarm Restore
QH
0
QHNN000000
3
220
00
000
LOC/Point ECS # Alarm
QA
Emergency #
QANN0E0000
1
220 +
Emer-
gency #
00
000
LOC/Point ECS # Alarm Restore
QH
Emergency #
QHNN0E0000
3
220 +
Emer-
gency #
00
000
Manual pull switch alarm
FA
Zone #
FANN000ZZZ
1
115
00
Zone #
Manual pull switch alarm restore
FH
Zone #
FHNN000ZZZ
3
115
00
Zone #
Manual pull switch trouble
FT
Zone #
FTNN000ZZZ
1
373
00
Zone #
Manual pull switch trouble restore
FJ
Zone #
FJNN000ZZZ
3
373
00
Zone #
Notification output trouble
FT
Group # + 1000
FTNN001GGG
1
320
00
Group #
Notification output trouble restore
FJ
Group # + 1000
FJNN001GGG
3
320
00
Group #
Positive Alarm Sequence acknowledge
switch trouble
FT
Zone #
FTNN000ZZZ
1
373
00
Zone #
Positive Alarm Sequence acknowledge
switch trouble restore
FJ
Zone #
FJNN000ZZZ
3
373
00
Zone #
SLC LED Module trouble
ET
0000
ETNN000000
1
333
00
000
SLC LED Module trouble restore
ER
0000
ERNN000000
3
333
00
000
Status Point Types Trouble
UT
0
UTNN000000
1
379
00
000
Status Point Types Trouble Restore
UJ
0
UJNN000000
3
379
00
000
Supervisory Detector Alarm
FS
Zone #
FSNN000ZZZ
1
200
00
Zone #
Supervisory Detector Alarm Restore
FR
Zone #
FRNN000ZZZ
3
200
00
Zone #
SIA Reporting Format
Contact ID Reporting Format
SIA pi Modifier
SIA
Event Description
Module ID
# (If Any)
SIA
Event
Codes
Parameter
Fixed Length
Format NN - panel
ID
XX- SBUS ID
ZZZ- Zone #
PPPP- Point #
GGG- Group #
E- Emergency #
RRRR-Receiver #
Qualifier
Event
Code
Group #
Contact #
Table 12.2 Report Formats Table (Continued)