Receivers Compatible with the Control Panel
Reporting
FCP-300/FCP-300ECS Manual —
P/N LS10145-002FK-E:A 3/12/2021
139
Supervisory/Tamper Alarm
FS
Zone #
FSNN000ZZZ
1
200
00
Zone #
Supervisory/Tamper alarm condition re-
store
FR
Zone #
FRNN000ZZZ
3
200
00
Zone #
Supervisory/Tamper switch trouble
FT
Zone #
FTNN000ZZZ
1
373
00
Zone #
Supervisory/Tamper switch
trouble restore
FJ
Zone #
FJNN000ZZZ
3
373
00
Zone #
System-based AUX1 switch alarm
UA
1000
UANN001000
1
140
01
000
System-based AUX1 switch alarm
restore
UH
1000
UHNN001000
3
140
01
000
System-based AUX1 switch trouble
UT
1000
UTNN001000
1
373
01
000
System-based AUX1 switch trouble re-
store
UJ
1000
UJNN001000
3
373
01
000
System-based AUX2 switch alarm
UA
2000
UANN002000
1
140
02
000
System-based AUX2 switch alarm restore
UH
2000
UHNN002000
3
140
02
000
System-based AUX2 switch trouble
UT
2000
UTNN002000
1
373
02
000
System-based AUX2 switch trouble re-
store
UJ
2000
UJNN002000
3
373
02
000
Voice Aux ECS 1 Alarm
UA
3
UANN003000
1
171
00
000
Voice Aux ECS 1 Alarm Restore
UH
3
UHNN003000
3
171
00
000
Voice Aux ECS 2 Alarm
UA
4
UANN004000
1
172
00
000
Voice Aux ECS 2 Alarm Restore
UH
4
UHNN004000
3
172
00
000
Voice Aux ECS 3 Alarm
UA
5
UANN005000
1
173
00
000
Voice Aux ECS 3 Alarm Restore
UH
5
UHNN005000
3
173
00
000
Voice Aux ECS 4 Alarm
UA
6
UANN006000
1
174
00
000
Voice Aux ECS 4 Alarm Restore
UH
6
UHNN006000
3
174
00
000
Water flow switch alarm
SA
Zone #
SANN000ZZZ
1
113
00
Zone #
Water flow switch alarm Restore
SH
Zone #
SHNN000ZZZ
3
113
00
Zone #
Water flow switch trouble
ST
Zone #
STNN000ZZZ
1
373
00
Zone #
Water flow switch trouble Restore
SJ
Zone #
SJNN000ZZZ
3
373
00
Zone #
Zone-based AUX1 switch alarm
UA
Zone # + 1000
UANN001ZZZ
1
140
01
Zone #
Zone-based AUX1 switch alarm restore
UH
Zone # + 1000
UHNN001ZZZ
3
140
01
Zone #
Zone-based AUX1 switch trouble
UT
Zone # + 1000
UTNN001ZZZ
1
373
01
Zone #
Zone-based AUX1 switch trouble restore
UJ
Zone # + 1000
UJNN001ZZZ
3
373
01
Zone #
Zone-based AUX2 switch alarm
UA
Zone # + 2000
UANN002ZZZ
1
140
02
Zone #
Zone-based AUX2 switch alarm restore
UH
Zone # + 2000
UHNN002ZZZ
3
140
02
Zone #
Zone-based AUX2 switch trouble
UT
Zone # + 2000
UTNN002ZZZ
1
373
02
Zone #
Zone-based AUX2 switch trouble restore
UJ
Zone # + 2000
UJNN002ZZZ
3
373
02
Zone #
Point Events
For FIK/SK devices, sensors 1–159 are reported as Points 1–159, modules 1–159 are reported as
Points 201–359.
An unexpected SLC device has been de-
tected
pi Exp. ID XE
Point #
XENNXXPPPP
1
380
Exp. ID
Point #
An unexpected SLC device has been re-
moved
pi Exp. ID XI
Point #
XINNXXPPPP
3
380
Exp. ID
Point #
Auxiliary power disabled
pi Exp. ID FB
Point #
FBNNXXPPPP
1
571
Exp. ID
Point #
Auxiliary power enabled
pi Exp. ID FU
Point #
FUNNXXPPPP
3
571
Exp. ID
Point #
Auxiliary power Trouble
pi Exp. ID FT
Point #
FTNNXXPPPP
1
320
Exp. ID
Point #
Auxiliary power trouble restore
pi Exp. ID FJ
Point #
FJNNXXPPPP
3
320
Exp. ID
Point #
Background Music Switch is Trouble
pi Exp. ID UT
Point #
UTNNXXPPPP
1
379
Exp. ID
Point #
Background Music Switch is Trouble Re-
stored
pi Exp. ID UJ
Point #
UJNNXXPPPP
3
379
Exp. ID
Point #
Background Music Switch is Disabled
pi Exp. ID UB
Point #
UBNNXXPPPP
1
580
Exp. ID
Point #
SIA Reporting Format
Contact ID Reporting Format
SIA pi Modifier
SIA
Event Description
Module ID
# (If Any)
SIA
Event
Codes
Parameter
Fixed Length
Format NN - panel
ID
XX- SBUS ID
ZZZ- Zone #
PPPP- Point #
GGG- Group #
E- Emergency #
RRRR-Receiver #
Qualifier
Event
Code
Group #
Contact #
Table 12.2 Report Formats Table (Continued)