Receivers Compatible with the Control Panel
Reporting
FCP-300/FCP-300ECS Manual —
P/N LS10145-002FK-E:A 3/12/2021
141
Interlock switch alarm restore (Water Re-
lease Zone)
pi Exp. ID FH
Point #
FHNNXXPPPP
3
110
Exp. ID
Point #
Interlock switch disabled
pi Exp. ID FB
Point #
FBNNXXPPPP
1
571
Exp. ID
Point #
Interlock switch enabled
pi Exp. ID FU
Point #
FUNNXXPPPP
3
571
Exp. ID
Point #
Interlock switch trouble (Water Release
Zone)
pi Exp. ID FT
Point #
FTNNXXPPPP
1
373
Exp. ID
Point #
Interlock switch trouble restore (Water Re-
lease Zone)
pi Exp. ID FJ
Point #
FJNNXXPPPP
3
373
Exp. ID
Point #
LOC Mic Activated ECS Alarm
pi Exp. ID QA
0
QANNXX0000
1
220
Exp. ID
000
LOC Mic Activated ECS Alarm Restore
pi Exp. ID QH
0
QHNNXX0000
3
220
Exp. ID
000
LOC ECS # Alarm
pi Exp. ID QA
Emergency #
QANNXXE000
1
220 +
Emer-
gency #
Exp. ID
000
LOC ECS # Alarm Restore
pi Exp. ID QH
Emergency #
QHNNXXE000
3
220 +
Emer-
gency #
Exp. ID
000
Manual pull switch alarm
pi Exp. ID FA
Point #
FANNXXPPPP
1
115
Exp. ID
Point #
Manual pull switch alarm restore
pi Exp. ID FH
Point #
FHNNXXPPPP
3
115
Exp. ID
Point #
Manual pull switch disabled
pi Exp. ID FB
Point #
FBNNXXPPPP
1
571
Exp. ID
Point #
Manual pull switch enabled
pi Exp. ID FU
Point #
FUNNXXPPPP
3
571
Exp. ID
Point #
Manual pull switch trouble
pi Exp. ID FT
Point #
FTNNXXPPPP
1
373
Exp. ID
Point #
Manual pull switch trouble restore
pi Exp. ID FJ
Point #
FJNNXXPPPP
3
373
Exp. ID
Point #
Manual release switch alarm
(Water Release Zone)
pi Exp. ID FA
Point #
FANNXXPPPP
1
110
Exp. ID
Point #
Manual release switch alarm restore (Wa-
ter Release Zone)
pi Exp. ID FH
Point #
FHNNXXPPPP
3
110
Exp. ID
Point #
Manual release switch disabled
pi Exp. ID FB
Point #
FBNNXXPPPP
1
571
Exp. ID
Point #
Manual release switch enabled
pi Exp. ID FU
Point #
FUNNXXPPPP
3
571
Exp. ID
Point #
Manual release switch trouble
(Water Release Zone)
pi Exp. ID FT
Point #
FTNNXXPPPP
1
373
Exp. ID
Point #
Manual release switch trouble restore
(Water Release Zone)
pi Exp. ID FJ
Point #
FJNNXXPPPP
3
373
Exp. ID
Point #
Notification output point disabled
pi Exp. ID FB
Point #
FBNNXXPPPP
1
571
Exp. ID
Point #
Notification output point enabled
pi Exp. ID FU
Point #
FUNNXXPPPP
3
571
Exp. ID
Point #
Notification output point trouble
pi Exp. ID FT
Point #
FTNNXXPPPP
1
320
Exp. ID
Point #
Notification output point trouble restore
pi Exp. ID FJ
Point #
FJNNXXPPPP
3
320
Exp. ID
Point #
Positive Alarm Sequence acknowledge
switch disabled
pi Exp. ID FB
Point #
FBNNXXPPPP
1
571
Exp. ID
Point #
Positive Alarm Sequence acknowledge
switch enabled
pi Exp. ID FU
Point #
FUNNXXPPPP
3
571
Exp. ID
Point #
Positive Alarm Sequence acknowledge
switch trouble
pi Exp. ID FT
Point #
FTNNXXPPPP
1
373
Exp. ID
Point #
Positive Alarm Sequence acknowledge
switch trouble restore
pi Exp. ID FJ
Point #
FJNNXXPPPP
3
373
Exp. ID
Point #
Status Point Trouble
pi Exp. ID UT
Point #
UTNNXXPPPP
1
379
Exp. ID
Point #
Status Point Trouble Restored
pi Exp. ID UJ
Point #
UJNNXXPPPP
3
379
Exp. ID
Point #
Status Point is Disabled
pi Exp. ID UB
Point #
UBNNXXPPPP
1
580
Exp. ID
Point #
Status Point is Enabled
pi Exp. ID UU
Point #
UUNNXXPPPP
3
580
Exp. ID
Point #
Supervisory/Tamper Alarm
pi Exp. ID FS
Point #
FSNNXXPPPP
1
200
Exp. ID
Point #
Supervisory/Tamper Alarm Restore
pi Exp. ID FR
Point #
FRNNXXPPPP
3
200
Exp. ID
Point #
Supervisory/Tamper point disabled
pi Exp. ID FB
Point #
FBNNXXPPPP
1
571
Exp. ID
Point #
SIA Reporting Format
Contact ID Reporting Format
SIA pi Modifier
SIA
Event Description
Module ID
# (If Any)
SIA
Event
Codes
Parameter
Fixed Length
Format NN - panel
ID
XX- SBUS ID
ZZZ- Zone #
PPPP- Point #
GGG- Group #
E- Emergency #
RRRR-Receiver #
Qualifier
Event
Code
Group #
Contact #
Table 12.2 Report Formats Table (Continued)
Summary of Contents for FCP-300
Page 169: ...Cut Along the Dotted Line ...
Page 171: ...Cut Along the Dotted Line ...
Page 173: ...Cut Along the Dotted Line ...
Page 175: ...Cut Along the Dotted Line ...