142
FCP-300/FCP-300ECS Manual —
P/N LS10145-002FK-E:A 3/12/2021
Reporting
Receivers Compatible with the Control Panel
Supervisory/Tamper point enabled
pi Exp. ID FU
Point #
FUNNXXPPPP
3
571
Exp. ID
Point #
Supervisory/Tamper point trouble
pi Exp. ID FT
Point #
FTNNXXPPPP
1
373
Exp. ID
Point #
Supervisory/Tamper point trouble
restore
pi Exp. ID FJ
Point #
FJNNXXPPPP
3
373
Exp. ID
Point #
System-based AUX1 switch alarm
pi Exp. ID UA
Point #
UANNXXPPPP
1
140
Exp. ID
Point #
System-based AUX1 switch alarm
restore
pi Exp. ID UH
Point #
UHNNXXPPPP
3
140
Exp. ID
Point #
System-based AUX1 switch disabled
pi Exp. ID UB
Point #
UBNNXXPPPP
1
571
Exp. ID
Point #
System-based AUX1 switch enabled
pi Exp. ID UU
Point #
UUNNXXPPPP
3
571
Exp. ID
Point #
System-based AUX1 switch trouble
pi Exp. ID UT
Point #
UTNNXXPPPP
1
373
Exp. ID
Point #
System-based AUX1 switch trouble
restore
pi Exp. ID UJ
Point #
UJNNXXPPPP
3
373
Exp. ID
Point #
System-based AUX2 switch alarm
pi Exp. ID UA
Point #
UANNXXPPPP
1
140
Exp. ID
Point #
System-based AUX2 switch alarm
restore
pi Exp. ID UH
Point #
UHNNXXPPPP
3
140
Exp. ID
Point #
System-based AUX2 switch disabled
pi Exp. ID UB
Point #
UBNNXXPPPP
1
571
Exp. ID
Point #
System-based AUX2 switch enabled
pi Exp. ID UU
Point #
UUNNXXPPPP
3
571
Exp. ID
Point #
System-based AUX2 switch trouble
pi Exp. ID UT
Point #
UTNNXXPPPP
1
373
Exp. ID
Point #
System-based AUX2 switch
trouble restore
pi Exp. ID UJ
Point #
UJNNXXPPPP
3
373
Exp. ID
Point #
Voice Aux ECS 1 Point Alarm
pi Exp. ID UA
(3PPP) PPP - Point # UANNXX3PPP
1
171
Exp. ID
Point #
Voice Aux ECS 1 Point Alarm Restore
pi Exp. ID UH
(3PPP) PPP - Point # UHNNXX3PPP
3
171
Exp. ID
Point #
Voice Aux ECS 2 Point Alarm
pi Exp. ID UA
(4PPP) PPP - Point # UANNXX4PPP
1
172
Exp. ID
Point #
Voice Aux ECS 2 Point Alarm Restore
pi Exp. ID UH
(4PPP) PPP - Point # UHNNXX4PPP
3
172
Exp. ID
Point #
Voice Aux ECS 3 Point Alarm
pi Exp. ID UA
(5PPP) PPP - Point # UANNXX5PPP
1
173
Exp. ID
Point #
Voice Aux ECS 3 Point Alarm Restore
pi Exp. ID UH
(5PPP) PPP - Point # UHNNXX5PPP
3
173
Exp. ID
Point #
Voice Aux ECS 4 Point Alarm
pi Exp. ID UA
(6PPP) PPP - Point # UANNXX6PPP
1
174
Exp. ID
Point #
Voice Aux ECS 4 Point Alarm Restore
pi Exp. ID UH
(6PPP) PPP - Point # UHNNXX6PPP
3
174
Exp. ID
Point #
Voice Aux ECS Point Trouble
pi Exp. ID UT
Point #
UTNNXXPPPP
1
379
Exp. ID
Point #
Voice Aux ECS Point Trouble Restore
pi Exp. ID UJ
Point #
UJNNXXPPPP
3
379
Exp. ID
Point #
Voice Aux ECS Point Disabled
pi Exp. ID UB
Point #
UBNNXXPPPP
1
580
Exp. ID
Point #
Voice Aux ECS Point Enabled
pi Exp. ID UU
Point #
UUNNXXPPPP
3
580
Exp. ID
Point #
Voice Aux Status 1 Switch is Trouble
pi Exp. ID UT
Point #
UTNNXXPPPP
1
379
Exp. ID
Point #
Voice Aux Status 1 Switch is
Trouble Restored
pi Exp. ID UJ
Point #
UJNNXXPPPP
3
379
Exp. ID
Point #
Voice Aux Status 1 Switch is Disabled
pi Exp. ID UB
Point #
UBNXXPPPP
1
580
Exp. ID
Point #
Voice Aux Status 1 Switch is Enabled
pi Exp. ID UU
Point #
UUNXXPPPP
3
580
Exp. ID
Point #
Voice Aux Status 2 Switch is Trouble
pi Exp. ID UT
Point #
UTNNXXPPPP
1
379
Exp. ID
Point #
Voice Aux Status 2 Switch is
Trouble Restored
pi Exp. ID UJ
Point #
UJNNXXPPPP
3
379
Exp. ID
Point #
Voice Aux Status 2 Switch is Disabled
pi Exp. ID UB
Point #
UBNNXXPPPP
1
580
Exp. ID
Point #
Voice Aux Status 2 Switch is Enabled
pi Exp. ID UU
Point #
UUNNXXPPPP
3
580
Exp. ID
Point #
Water flow switch alarm
pi Exp. ID SA
Point #
SANNXXPPPP
1
113
Exp. ID
Point #
Water flow switch alarm restore
pi Exp. ID SH
Point #
SHNNXXPPPP
3
113
Exp. ID
Point #
Water flow switch disabled
pi Exp. ID SB
Point #
SBNNXXPPPP
1
571
Exp. ID
Point #
Water flow switch enabled
pi Exp. ID SU
Point #
SUNNXXPPPP
3
571
Exp. ID
Point #
Water flow switch trouble
pi Exp. ID ST
Point #
STNNXXPPPP
1
373
Exp. ID
Point #
Water flow switch trouble restore
pi Exp. ID SJ
Point #
SJNNXXPPPP
3
373
Exp. ID
Point #
Zone-based AUX1 switch alarm
pi Exp. ID UA
Point #
UANNXXPPPP
1
140
Exp. ID
Point #
Zone-based AUX1 switch alarm restore
pi Exp. ID UH
Point #
UHNNXXPPPP
3
140
Exp. ID
Point #
Zone-based AUX1 switch disabled
pi Exp. ID UB
Point #
UBNNXXPPPP
1
571
Exp. ID
Point #
SIA Reporting Format
Contact ID Reporting Format
SIA pi Modifier
SIA
Event Description
Module ID
# (If Any)
SIA
Event
Codes
Parameter
Fixed Length
Format NN - panel
ID
XX- SBUS ID
ZZZ- Zone #
PPPP- Point #
GGG- Group #
E- Emergency #
RRRR-Receiver #
Qualifier
Event
Code
Group #
Contact #
Table 12.2 Report Formats Table (Continued)
Summary of Contents for FCP-300