SIA - FCP-300/ECS Panels PI Modifier Contact Reporting:
Reporting
FCP-300/FCP-300ECS Manual —
P/N LS10145-002FK-E:A 3/12/2021
143
12.2 SIA - FCP-300/ECS Panels PI Modifier Contact Reporting:
Events are sent to the Central Station as a variable length string:
The event format is:
EEZZZZ
Where:
EE Event code (2 characters)
ZZZZ Event parameter (up to four digits – not zero filled)
1.
The account number is sent using an account block that is separate from the event block
2.
Multiple events can be sent within a single event block. Events are separated by a “/” character.
3.
Event parameter can be either a zone, point or module number.
4.
When reporting by point is enabled, the communicator uses a “pi” event to supersedes the actual point event to report the
module the point is linked to.
5.
Panel ID is not sent in the SIA event parameters.
For Example see Table 12.3:
Zone-based AUX1 switch enabled
pi Exp. ID UU
Point #
UUNNXXPPPP
3
571
Exp. ID
Point #
Zone-based AUX1 switch trouble
pi Exp. ID UT
Point #
UTNNXXPPPP
1
373
Exp. ID
Point #
Zone-based AUX1 switch trouble restore pi Exp. ID UJ
Point #
UJNNXXPPPP
3
373
Exp. ID
Point #
Zone-based AUX2 switch alarm
pi Exp. ID UA
Point #
UANNXXPPPP
1
140
Exp. ID
Point #
Zone-based AUX2 switch alarm restore
pi Exp. ID UH
Point #
UHNNXXPPPP
3
140
Exp. ID
Point #
Zone-based AUX2 switch disabled
pi Exp. ID UB
Point #
UBNNXXPPPP
1
571
Exp. ID
Point #
Zone-based AUX2 switch enabled
pi Exp. ID UU
Point #
UUNNXXPPPP
3
571
Exp. ID
Point #
Zone-based AUX2 switch trouble
pi Exp. ID UT
Point #
UTNNXXPPPP
1
373
Exp. ID
Point #
Zone-based AUX2 switch trouble restore pi Exp. ID UJ
Point #
UJNNXXPPPP
3
373
Exp. ID
Point #
System-based Wireless Gateway Trouble pi Exp. ID UT
Point #
UTNNXXPPPP
1
373
Exp. ID
Point #
System-based Wireless Gateway Trouble
- restore
pi Exp. ID UJ
Point #
UJNNXXPPPP
3
373
Exp. ID
Point #
Wireless Gateway Trouble
pi Exp. ID UT
Point #
UTNNXXPPPP
1
373
Exp. ID
Point #
Wireless Gateway Trouble restore
pi Exp. ID UJ
Point #
UJNNXXPPPP
3
373
Exp. ID
Point #
SIA Reporting Format
Contact ID Reporting Format
SIA pi Modifier
SIA
Event Description
Module ID
# (If Any)
SIA
Event
Codes
Parameter
Fixed Length
Format NN - panel
ID
XX- SBUS ID
ZZZ- Zone #
PPPP- Point #
GGG- Group #
E- Emergency #
RRRR-Receiver #
Qualifier
Event
Code
Group #
Contact #
Table 12.2 Report Formats Table (Continued)
Event
Report
Zone/ Point
Panel ID Module Zone ZZZZ Point ZZZZ
Fields Sent
SIA Event
Data
Fire Alarm-Zone
Zone
n/a
n/a97
15
n/a
EE-ZZ
FA15
Fire Alarm-Zone
Zone
n/a
n/a
05
n/a
EE-Z
FA5
Fire Alarm-Point
Point
n/a
01
n/a
123
EE-ZZ /EE-ZZZ pi01/FA123
Fire Alarm-Point
Point
n/a
33
n/a
203
EE-ZZ /EE-ZZZ pi11/FA203
Expander Trouble
n/a
n/a
11
n/a
n/a
EE-ZZ
ET11
Auto Test
n/a
n/a
n/a
n/a
n/a
EE-Z
RP0
Battery Trouble-Panel 32
n/a
n/a
98
n/a
n/a
EE-ZZ
YT98
Battery Trouble-Expander 18 n/a
n/a
18
n/a
n/a
EE-ZZ
YT18
SLC Loop Shorted
n/a
n/a
44
n/a
n/a
EE-ZZ
ET44
Program Begin Panel ID=32
n/a
n/a
n/a
n/a
n/a
EE-Z
LB0
Program Begin Panel ID= 22
n/a
n/a
n/a
n/a
n/a
EE-Z
LB0
AC Power Loss - Panel 22
n/a
n/a
98
n/a
n/a
EE-Z
AT0
Fire Trouble
Point
n/a
97
n/a
200
EE-ZZ /EE-ZZZ pi97/FT200
Fire Trouble
Zone
n/a
97
01
n/a
EE-Z
FT1
Fire Trouble-Nac
Point
n/a
98
n/a
Nac Circuit 7 EE-ZZ /EE-Z
pi98/FT7Z=Pt. #
Table 12.3 SIA- Panels - PI Modifier Reporting Examples