Reporting
SIA – Panel Communicator:
12.3 SIA – Panel
Communicator:
(Differences/additional features are underlined)
Events are sent to the Central Station Receiver as a fixed length string:
The event format is:
EEPPMMZZZZ
Where
EE Event code (2 characters)
PP Panel number (2 digits – Zero Filled) (valid range from 1 to 64)
MM Module number (2 digits – Zero Filled) (valid range from 1 to 98, typically
Module information)
ZZZZ Event parameter (4 digits – Zero Filled) (typically Point, Zone or Circuit
information)
1.
The Event field will contain 10 digits including the 2 digit event code (EE), 2 digit panel ID (PP), 2 digit Module Number
(MM) and a 4 digit Event Parameter (ZZZZ).
2.
Based on the actual Event Code, the Module Number or Event Parameter fields might not contain pertinent information.
In that case the field will contain zeros.
3.
The account number is sent using an account block that is separate from the event block.
4.
Multiple events can be sent within a single event block. Events are separated by a “/” character.
5.
Event parameter can be a Zone, Point or Circuit Number.
6.
“pi” modifier event is not used.
7.
Panel can be set to report by either Point or Zone.
Fire Trouble-Nac
Zone
n/a
98
n/a
Nac Circuit 7 EE-ZZZ
FT400
ZZZ=OPG#
Event
Report
Zone/ Point
Panel ID Module Zone ZZZZ Point ZZZZ
Fields Sent
SIA Event
Data
Table 12.3 SIA- Panels - PI Modifier Reporting Examples
Event
Report
Zone/
Point
Panel ID
PP
Module
MM
Zone
ZZZZ
Point
ZZZZ
Fields
Sent
SIA Event
Data
Fire Alarm-Zone
Zone
32
n/a
15
n/a
EE-PP-MM-ZZZZ FA32000015
Fire Alarm-Zone
Zone
32
n/a
05
n/a
EE-PP-MM-ZZZZ
FA32000005
Fire Alarm-Point
Point
32
01
n/a
123
EE-PP-MM-ZZZZ
FA32010123
Fire Alarm-Point
Point
21
33
n/a
203
EE-PP-MM-ZZZZ
FA21330203
Expander Trouble
n/a
15
11
n/a
n/a
EE-PP-MM-ZZZZ
ET15110000
Auto Test
n/a
32
n/a
n/a
n/a
EE-PP-MM-ZZZZ
RP32000000
Battery Trouble-Panel 32
n/a
32
98
n/a
n/a
EE-PP-MM-ZZZZ
YT32980000
Battery Trouble-Expander 18
n/a
32
18
n/a
n/a
EE-PP-MM-ZZZZ
YT32180000
SLC Loop Shorted
n/a
01
44
n/a
n/a
EE-PP-MM-ZZZZ
ET01440000
Program Begin
n/a
32
n/a
n/a
n/a
EE-PP-MM-ZZZZ
LB32000000
Program Begin
n/a
22
n/a
n/a
n/a
EE-PP-MM-ZZZZ
LB22000000
AC Power Loss- Panel 22
n/a
22
98
n/a
n/a
EE-PP-MM-ZZZZ
AT22980000MM = 00
Fire Trouble
Point
22
97
n/a
200
EE-PP-MM-ZZZZ
FT22970200
Fire Trouble
Zone
22
97
1
n/a
EE-PP-MM-ZZZZ
FT22970001
MM = 00
Fire Trouble-Nac
Point
22
98
n/a
Nac Circuit 7 EE-PP-MM-ZZZZ
FT22980007ZZZZ=Pt. #
Fire Trouble-Nac
Zone
22
98
n/a
Nac Circuit 7 EE-PP-MM-ZZZZ
FT22980007
ZZZZ=OPG #
Table 12.4 SIA Reporting Examples