Calculating Current Draw and Standby Battery
Installation Requirements
FCP-300/FCP-300ECS Manual —
P/N LS10145-002FK-E:A 3/12/2021
21
Addressable SLC Devices
FIK-M500M
Standby/Alarm: .375 mA
mA
mA
FIK-M501M
mA
mA
FIK-PULL-SA / FIK-PULL-DA
mA
mA
FIK-M500DM
Standby/Alarm: .75 mA
mA
mA
FIK-IM-10
Standby/Alarm: 3.5 mA
mA
mA
FIK-M500X
SLC
Standby: 375 mA
Alarm: .375 mA
mA
mA
Aux. Power Standby: 1.7 mA
mA
Alarm: 7 mA
mA
FIK-SC-6
SLC
Standby: 2.25 mA
Alarm: 2.25 mA
mA
mA
Aux. Pwr
Standby: 8 mA
Alarm: 20 mA
mA
mA
FIK-M500R
Standby/Alarm: .255 mA
mA
mA
FIK-CR-6
Standby/Alarm: 1.45 mA
mA
mA
FIK-M500MR-2
Standby: 1.3 mA
mA
Alarm: 24 mA
mA
FIK-M502M
Aux Pwr
Standby: 12 mA
mA
Alarm: 90 mA
mA
SLC
Standby/Alarm: 2 mA
mA
mA
FIK-CZ-6
Aux Pwr
Standby: 70 mA
mA
Alarm: per zone 90 mA
mA
Alarm: Total with all 6 circuits
active 540 mA
mA
SLC
Standby/Alarm: 2 mA
mA
mA
SLC Accessories
B200SR / IV / WH Sounder Base
Aux Pwr
Standby: .5mA
mA
Alarm: 35mA
mA
SLC
Standby 3mA
mA
B200S / IV / WH intelligent Sounder Base
Aux Pwr
Standby: .5mA
mA
Alarm: (high vol) 35mA
mA
SLC
Standby .3mA
mA
B200SR-LF / IV / WH Low Frequency
Sounder Base
Aux Pwr
Standby: 1mA
mA
Alarm: 125mA
mA
B200S-LF/ IV / WH Low Frequency
Sounder Base
Aux Pwr
Standby .55mA
mA
Alarm (high vol) 140mA
mA
SLC
Standby .30mA
mA
B224RB / IV /WH Relay Base
Standby/Alarm: .5mA
mA
mA
RTS151/151 KEY
Alarm: 7.5 mA
mA
RA100Z
Alarm: 10 mA
mA
SLC Isolator Devices
FIK-M500X (Isolator Module)
(100 max.)
Standby/Alarm: .45 mA
mA
mA
B224BI/IV Isolator Base
Standby/Alarm: .5 mA
Accessories Modules
FIK-6815 SLC Loop Expander
(63 max.)
Standby/Alarm: 78 mA
mA
mA
Color Guide: -WH = White, -IV = Ivory
FIK-RA2000 Remote LCD Annunciator
(16 max.)
Standby: 25 mA
mA
Alarm: 50 mA
mA
FIK-RA1000 Remote LCD Annunciator
Standby: 20 mA
mA
Alarm: 25 mA
mA
FIK-RA100 Remote LCD Annunciator
Standby: 20 mA
mA
Alarm: 25 mA
mA
FIK-5824 Serial / Parallel Module
(4 max.)
Standby/Alarm: 45 mA
mA
mA
FIK-RPS1000 Power Supply
(16 max.)
Standby/Alarm: 10 mA
mA
mA
FIK-5496 NAC Expander
Standby/Alarm: 10 mA
mA
mA
Device
Number of
Devices
Current per Device
Standby
Current
Alarm Current
Table 3.3 Current Draw Worksheet for Fike SLC Devices (Continued)
Summary of Contents for FCP-300