22
FCP-300/FCP-300ECS Manual —
P/N LS10145-002FK-E:A 3/12/2021
Installation Requirements
Calculating Current Draw and Standby Battery
1. The FACP can only support 5 devices w/LED’s on. This current draw is added to the panels alarm current.
2. IDP-Beam-T draws a maximum of 500mA from Auxiliary power only when the test feature is used. This should be consid-
ered when determining auxiliary power capacity but not calculated into current requirements for day to day operation.
3. The FIK-2351R is sold separately from the DNR. Current draw for the DNR + FIK-2351R is calculated by increasing the
“Number of Devices” column for each FIK-2351R used with a DNR.
4. The DNR housing does not include a Relay circuit board. If a relay is needed, be sure to add one to the FIK-M500R and
FIK-2351R “Number of Devices” column for each DNR used for correct current calculations.
5. If you use the door holders, you do not need to consider the door holder current for the alarm/battery standby, because the
power is removed during that time. However, during normal operation, the door holders draw current and must be included
in the 6.0A total current that can be drawn from the panel.
FIK-5865-4 LED Annunciator Module
(with reset and silence switches)
(8 max.)
Standby: 35 mA
mA
Alarm: 145 mA
mA
FIK-5865-3 LED Annunciator Module
Standby: 35 mA
mA
Alarm: 145 mA
mA
FIK-5880 LED I/O Module
Standby: 35 mA
mA
Alarm: 200 mA
mA
FIK-5883 Relay Interface
(32 max.)
Standby: 0 mA
mA
Alarm: 220 mA
(22 mA per relay)
mA
FIK-50W or FIK-125W Audio Amplifier
with/without FIK-CE4
(8 max.)
Standby: 10 mA
mA
Alarm: 10 mA
mA
FIK-DUAL50W
(8 max.)
Standby/Alarm: 10 mA
mA
mA
FIK-50WBU
(8 max.)
Standby/Alarm: 10 mA
mA
mA
FIK-INT50W Internal Amplifier
(8 max.)
Standby: 52 mA
mA
Alarm @ 25V: 275 mA
mA
Alarm @ 70V: 310 mA
mA
FIK-NVCM Network Voice Control
Module
(1 max.)
Standby/Alarm: 59 mA
mA
mA
FIK-SW24 Switch Expander
(8 max.)
Standby: 10 mA
mA
Alarm: 25 mA
mA
FIK-RPU Remote Paging Unit
(7 max.)
Standby: 70 mA
mA
Alarm: 100 mA
mA
FIK-LOC Local Operating Console
(includes FIK-RA2000, FIK-RVM &
FIK-SW-24)
(7 max.)
Standby: 100 mA
mA
Alarm: 150 mA
mA
Network Cards
FIK-NIC Network Interface Card
(1 Max.)
Standby/Alarm: 21 mA
mA
mA
FIK-FML Fiber-Optic Multi Mode
(1 Max.)
Standby/Alarm: 53 mA
mA
mA
FIK-FSL Fiber-Optic Single Mode
(1 Max.)
Standby/Alarm: 79 mA
mA
mA
A Total System Current
Wireless Modules
FIK-W-WGI Wireless Gateway
Max current using ext supply 40 mA
mA
mA
Max current SLC Power 24 mA
mA
mA
Total System Current
Auxiliary Devices
5
Refer to devices manual for current rating.
B Auxiliary Devices Current
Notification Appliance Circuits
Refer to devices manual for current rating.
C Notification Appliances Current:
mA
D Total current ratings of all devices in System (line A + line B + C)
mA
mA
E Total current ratings converted to amperes (line D x .001):
A
A
F Number of standby hours (24 or 60 for NFPA 72, chapter 1, 1-5.2.5):
H
G Multiply lines E and F.
Total standby AH
AH
H Alarm sounding period in hours. (For example, 5 minutes = .0833 hours)
H
I
Multiply lines E and H.
Total alarm AH
AH
J
Add lines G and I.
6
AH
Multiply by the Derating Factor
x 1.25
Total ampere hours required
Device
Number of
Devices
Current per Device
Standby
Current
Alarm Current
Table 3.3 Current Draw Worksheet for Fike SLC Devices (Continued)