30
FCP-300/FCP-300ECS Manual —
P/N LS10145-002FK-E:A 3/12/2021
Control Panel Installation
FIK-RA100 Remote Annunciator Installation
4.5 FIK-RA100 Remote Annunciator Installation
The optional Model FIK-RA100 Remote Annunciator, is shown in Figure 4.9. The FIK-RA100 can be surface or flush
mounted. Up to 16 FIK-RA100s can be added to the FCP-300/ECS System.
Figure 4.9 Model FIK-RA100 Remote Annunciator, Front View
The FIK-RA100 installation involves the following steps:
1.
Make sure power is off at the panel.
2.
Mount the FIK-RA100 in the desired location (see Section 4.5.1).
3.
Connect the FIK-RA100 to the panel (see Section 4.4.2).
4.
Use the DIP switches on the back of the FIK-RA100 to assign an ID# to the FIK-RA100 (see Section 4.12.1).
5.
The new FIK-RA100 module must be added to the System through programming.
JumpStart
®
will add the module automatically (see Section 8.1). You can also add it manually (see Section 9.2.2).
6.
Select a name, if desired (See “Editing Module ID” on page 121.).
4.5.1 Mounting the FIK-RA100
This Section of the manual describes the procedure to mount the remote annunciator. The annunciator can be flush- or surface-
mounted.
Flush Mounting
This Section of the manual describes flush mounting. Follow these steps to flush mount the FIK-RA100. The back box dimen-
sions are 9-9/32” w x 8-3/8” h. The minimum is depth 2". The back box can be mounted before you complete the installation
of the FIK-RA100 using any of the mounting holes shown in Figure 4.10.
Figure 4.10 Back Box Mounting Holes
7.
Remove knockout holes as needed for wires. See Figure 4.11 for backbox knockout locations.
Mounting Holes
Mounting Holes