Using the Addressable Relay Module for City Box Connection
Control Panel Installation
FCP-300/FCP-300ECS Manual —
P/N LS10145-002FK-E:A 3/12/2021
51
4.
Program the NAC circuit used as a continuous and non-silencing. Refer to Section 9.5 for point programming, Section 9.4
for group settings, and Section 9.3 for zone settings and mapping. It is not possible to reset the remote indication until you
clear the condition and reset the control panel.
Figure 4.45 City Box Connection
4.17 Using the Addressable Relay Module for City Box Connection
Wire the Relay module as shown in Figure 4.46.
Figure 4.46 Relay Module for City Box Connection
Note:
NAC Circuit 2 Used
as an example.
Any NAC circuit
could be used.
Non-Supervised
Non-Power Limited
Intended for
connection to a
Note: The shunt connection is recognized only as a supple-
mentary signaling unit as part of a local control unit and is
not recognized as an auxiliary control unit connection per
UL listed EOL
must be
Installed in City
Box
Enclosure