Network Management
Network Programming
To Edit the Network Panel ID, do the following.
1.
Enter the Installer Code. The panel will automatically access the Main Menu.
2.
Select 6 for the Network Programming.
3.
Press 3 to enter the Edit Panel ID Menu.
4.
If the Network Panel ID is changed and valid, the System will prompt you to confirm the change. If it is not correct, you
can change the Dip Switches at this time.
5.
To select YES, press the up arrow. To confirm, press ENTER
6.2.4 Computer Access
An Installer at the panel site can initiate the communications between the panel and a computer running the HFSS Program-
ming Tool (see also Section 10.5). In order for this communication to function properly, both the computer (running the soft-
ware) and the control panel must have matching computer access numbers and computer codes.
To program computer access information:
1.
Enter the Installer Code. The panel will automatically access the Main Menu.
2.
Select 6 for the Network Programming.
3.
Press 4 to enter the Computer Access Menu.
4.
Enter the computer access number (up to 6-digits), then press ENTER.
5.
Enter the computer code, then press ENTER.
6.
Enter the computer phone number, the panel will dial to connect to a downloading computer (up to 40-digits), then press
ENTER.
6.2.5 Access Codes
The Access Codes provide the user access to the control panel functions. Each Access Code can be customized for each user.
This feature allows some users the ability to access the programming and other higher level panel functions, while other users
may only need to access the lower level functions such as, preforming fire drills, or acknowledging trouble conditions.
Profile 1 is the profile that dictates what functions to which the Fire Fighter Key has access. Because this is the profile for a
key, the user name and the access code can not be edited for this profile.
Profile 2 is the profile used for the installer and is referred to as the “Installer Code”. This profile’s user name and panel func-
tions can not be edited. Table 6.1 lists the panel functions that can be selected for each user profile.
Type of Function
Selectable Functions
Panel Operations
System Reset
System Silence
System Ack
Fire Drill Key
Multi-site
F1 Function Key
F2 Function Key
F3 Function Key
F4 Function Key
ECS Control Request Function
ECS Super User Function
Panel Menus
System Tests
Fire Drill Menu
Indicator Test
Walk Test-No Report
Walk Test -With Report
Communicator Test
Clear History Buffer
Point Functions
Disable/Enable Point
Point Status
Set SLC Device Address
SLC Single Device Locator
SLC Multiple Device Locator
I/O Point Control
Event History
Set Time & Date
System Information
Network Diagnostics
Network Programming
Panel Programming
Send/Receive Firmware Update
Table 6.1
User Profile Selectable Panel Functions
Summary of Contents for FCP-300
Page 169: ...Cut Along the Dotted Line ...
Page 171: ...Cut Along the Dotted Line ...
Page 173: ...Cut Along the Dotted Line ...
Page 175: ...Cut Along the Dotted Line ...