Group
9.3.2 View Zone Points
To view the points in a zone, follow these steps:
1.
Enter the Installer Code. The panel will automatically access the Main Menu.
2.
Select 7 for the Panel Programming.
3.
Press 2 to enter the Zone Menu.
4.
Press 2 to view the Zone Points.
5.
Enter the number of the zone you want to view, then press ENTER
9.4 Group
An output group is made up of output points that are programmed to respond in the same way. The Output groups simplify pro-
gramming because you only have to program the output characteristics that are common to all of the group points once, instead
of programming each individual point. After you defined the characteristics of output groups, you can assign each point to the
appropriate group. All valid output points are assigned to only one output group. Unused points are not assigned to any output
group. Up to 250 output groups can be defined per panel.
9.4.1 Edit Group
In the Edit Group option, you can program the name of an output group and change the properties of that group.
To edit a group, follow these steps:
1.
Enter the Installer Code. The panel will automatically access the Main Menu.
2.
Select 7 for the Panel Programming.
3.
Press 3 to enter the Group Menu.
4.
Press 1 to edit the group.
5.
Enter the number of the group you want to edit, then press ENTER.
Edit Group Name
6.
To edit the group name, press 1.
You can enter text to label a descriptive name for a group to appear on the display .
Edit Group Properties
7.
To edit the Group Properties, press 2 from the Edit Group Menu.
•
Select Y for the voice group and N for the non-voice group.
•
Select / Dynamic Activation Switch Number: used when the group is defined as a voice group; or as a non-voice group
where the Dynamic Activation is used.
This option links the output group with a voice select switch on an FIK-RVM, or a switch expander for dynamic
activation/deactivation.
•
Template Override - Is shown when it is set to Yes.
•
Dynamic Activation -Is shown if a non-voice group is assigned to a Select/Dynamic Activation Switch Number.
•
Dynamic Activation / Template Override Cadence. (This is shown when the Template override is set to Yes or if a non-
voice group is assigned a Select/Dynamic Activation switch number): this setting sets the cadence of the non-voice group
mapped to voice select switch when activated using dynamic activation or by a template.
Defining Output Group Type
Each output group is defined as either a voice output group or a non-voice output group.
•
Output points that are audio circuits (all circuits on the FIK-50W, FIK-125W, FIK-DUAL-50W, FIK-INT50W and FIK-
CE4) can be assigned to only voice output groups.
•
Output points that are non-voice circuits (all other points and circuits that are on all modules, except the FIK-50W, FIK-
125W, FIK-DUAL-50W, FIK-INT50W and FIK-CE4) are assigned to non-voice output groups.
Each of the output groups, defined as a voice, can be mapped to a particular switch and LED on the FIK-NVCM, FIK-RVM
and FIK-SW24. This allows the user to see the state of the voice groups assigned to the switches.
This also lets the user to individually select which areas they want to do a live page into. Output groups, not defined as voice
groups, can also be assigned to these switches as long as there is a voice group already assigned to the group. This allows for
dynamically activating/deactivating both voice and strobes/other outputs in an area with a single button press. See “Activat-
ing/Deactivating Output Groups Dynamically” on page 162.
NOTE:
If the SLC protocol is changed to Fike-IDP, the FIK Series and the cadence is no longer valid for Fike. The Zone Cadence will be
set to constant ON.
NOTE:
See Appendix B for editing names.
NOTE:
These settings only apply to non-voice groups.