98
FCP-300/FCP-300ECS Manual —
P/N LS10145-002FK-E:A 3/12/2021
Programming
Point
9.5 Point
You may need to change the characteristics of individual input points (detectors and switches) even after using JumpStart. This
Section explains how to change options for: type of input point; latching/non-latching status (switches); and name and
zone/group assignment of a point.
9.5.1 Point Programming For FIK-6815 Module
To program for points on an FIK-6815 module, follow these steps:
1.
Enter the Installer Code. The panel will automatically access the Main Menu.
2.
Select 7 for Panel Programming.
3.
Press 4 to enter the Point Menu.
4.
Press the up or down arrow key to select the desired module. Refer to Section 8.5 Quick Reference Table for available
choices. Then press ENTER.
5.
Select S for sensor or select M for module. (FIK or SK Only)
6.
Enter the number of the point you want to edit, then press ENTER.
7.
Select the type of device by pressing the up or down arrow key. Refer to Table 9.5 under the column heading “Type
Selection” for a list of choices.
Type Selection
Function
Latching Option
Comments
UNUSED
Select for SLC points that are unused.
DETECTOR
PHOTO
Spot photoelectric detectors.
ION
Spot ionization detector.
HEAT
Spot heat detector.
PHOTO DUCT
Duct photoelectric detector.
ACCLIMATE
Acclimate photoelectric detector.
HEAT HT
High temperature heat detector.
PHOTO-HEAT
Photoelectric detector with heat sensor.
BEAM
Beam smoke detector.
2-WIRE SMOKE
2-wire smoke detector.
SUP DET
PHOTO
Latching
Non Latching
Use this option when you want a detector to indicate a supervisory
alarm.
ION
HEAT
PHOTO DUCT
ACCLIMATE
HEAT HT
PHOTO-HEAT
BEAM
CO SMOKE
DETECTOR
CO ALRM /
FIRE ALRM
CO ALRM /
FIRE SUPR
CO SUPR /
FIRE ALRM
CO SUPR /
FIRE SUPR
Latching
Non Latching
Supervisory switches can be latching or non-latching.
W-DETECTOR PHOTO
Latching
Non Latching
Wireless photoelectric detectors.
ACCLIMATE (FIK)
Wireless acclimate photoelectric detector.
PHOTO-HEAT (SK)
Wireless heat detector.
HEAT
W-SUP DET
Same as W-
Detector
Latching
Non Latching
Wireless photoelectric detectors.
Table 9.5 Programming Options for FIK-6815 Modules