Amplifier Programming
Emergency Communication System Operation
FCP-300/FCP-300ECS Manual —
P/N LS10145-002FK-E:A 3/12/2021
129
11.4.2 FIK-NVCM & FIK-RVM Points
The FIK-NVCM and FIK-RVM modules contain two programmable input points. These modules also have the ability to be
programmed as a trigger for bringing the external audio into the System. These special point types are: Voice Aux ECS and
Voice Aux Status. When activated, if the event has the highest Event Priority of all activated events, these points will activate
the Aux In input to all outputs defined by the respective Event Program Mapping.
11.5 Amplifier Programming
11.5.1 Adding an Amplifier
To add a new AMP to the System, follow these steps:
1.
Enter the Installer Code. The panel will automatically go to the Main Menu.
2.
Select 7 for Panel Programming menu.
3.
Press 1 to enter Module Menu.
4.
Press 2 to add a module.
5.
From the next screen, add an FIK-AMP.
The screen will display “Adding module [#]...” for a few moments. You will be returned to the <New Module Type>
screen where you can select another a name for the module(s) if desired.
You must save changes when you exit the Program Menu or the new module will not be added. For more information see sec-
tion
.
If you Add a Module that has not been physically connected, the panel will go into trouble after it re-initializes (when you exit
the Program Menu with changes accepted). When the new module is attached, the trouble will restore automatically the next
time you power up the FACP.
11.5.2 Editing an Amplifier
When you edit the AMPs, the following features may be edited:
To edit an existing module, do the following.
1.
Enter the Installer Code. The panel will automatically access the Main Menu.
2.
Select 7 for the Program Menu.
3.
Press 1 to enter the Module Menu.
4.
Press 1 to edit a module.
5.
Use the up or down arrow key to select the module you want to edit.
6.
Press the right arrow key or press ENTER to move the cursor to the next selection.
11.6 LOC Programming
The Device Priority is a programmable option that can be programmed for each of the ECS devices:
•
FIK-NVCM
•
FIK-RVM
Each Device Priority is assigned a priority level: Low, Normal, or High.
11.6.1 Adding an LOC
To add the new ECS hardware modules to the System, refer to the following steps.
You must be in the Main Menu to perform this task.
1.
Enter the Installer Code.
2.
Select 7 for the Program Menu.
3.
Press 1 to enter the Module Menu.
4.
Press 2 to add a module.
5.
From the next screen, add either an FIK-NVCM* or FIK-RVM**.
* Only 1 FIK-NVCM may be installed per site.
** Up to 15 FIK-RVMs may be installed per site.
The screen will display “Adding module [#]...” for a few moments. The System will return to the <New Module Type>
screen where you can select a name for the module if desired.
6.
Add a LCD Annunciator, if desired, to associate with each FIK-NVCM or FIK-RVM.
You must save the changes before you exit the Program Menu or the new module will not be added. For more information, see
NOTE:
Background Music is only allowed to be mapped to circuit 8 of the FIK-DUAL50W amplifiers to ensure correct active supervision.
•
module ID •
module name •
amplifier module
•
FIK-CE4 installed (Yes or No) •
output voltage
NOTE:
If you Add a Module that has not been physically connected, the panel will go into trouble after it re-initializes (when you exit the
Program Menu). When the new module is attached, the trouble will correct itself automatically the next time you power up the System.