FCP-300/FCP-300ECS Manual —
P/N LS10145-002FK-E:A 3/12/2021
Control Panel Installation
Notification Appliance/Auxiliary Power Circuits
2.
Configure the circuit for Class A in programming (see Section 9.5).
Figure 4.42 Class A Notification Appliance Circuit Configuration
4.14.2 Auxiliary Power Installation
The NAC Circuits 1-4 on the control panel can be used as auxiliary power circuits. The four types of auxiliary power available
are as follows.
The Auxiliary power circuits are power-limited. Each circuit can source up to 3A (total current for all NAC circuits must not
exceed 6A).
To install an auxiliary power circuit, do the following.
1.
Wire the NAC circuit(s) that will be used for the auxiliary power. See Figure 4.42 for location of NAC circuits.
2.
Configure the auxiliary power output through the programming (see section Section 9.5).
Door Holder Power
The Door Holder Power is intended to be used with the fire door applications. When there are no alarms in the System and the
panel has AC power, the door holder circuits have a 24-volt power present at their terminals. Any alarm will cause power to
disconnect. The power will be re-applied when the System is reset. If the AC power is off for more than 15 seconds, the auxil-
iary door holder power will be disconnected to conserve the battery backup. When the AC power is restored, the power is
immediately restored to the door holder circuits.
Constant Power
Use the Constant Power for the applications that require a constant auxiliary power source. The power is always present at
Constant circuits.
Resettable Power
The Resettable Power is typically used to power the beam detectors, flame detectors and conventional 4-wire smoke detectors.
For circuits selected as Resettable, 24-volt power is always present at the terminals unless a System reset occurs. If a System
reset occurs, power is disconnected from the terminals for 30 seconds, then re-applied.
Sounder Sync Power
The Sounder Sync Power continuously outputs the System Sensor synchronization pattern and is intended for use with the
B200S sounder bases.
Supervised
Power-Limited
Max. Impedance: 1.5
Ω
All Circuits are Synchronized
(Regulated). Rated @ 27.4
VDC @ 3A Max.
•
Door Holder
•
Constant
•
Resettable Power
•
Sounder Sync Power