Using the Addressable Relay Module for City Box Connection
Control Panel Installation
FCP-300/FCP-300ECS Manual —
P/N LS10145-002FK-E:A 3/12/2021
53
To install the 7644-L8 for polarity reversal:
1.
Wire the 7644-L8 to the control panel as shown in Figure 4.48. Do not install an EOL resistor on the terminals of the
NAC circuit used.
2.
Program the NAC circuit as a notification circuit. See Section 9.5.4.
3.
Map the group to activate the constant on from the zone event.
4.
Program the output group characteristics as non-silenceable and reverse polarity.
Figure 4.48 Polarity Reversal Connection Using the 7644-L8
NOTE:
Use only NAC circuits on the control panel for reverse polarity