Voice Options
Network Management
FCP-300/FCP-300ECS Manual —
P/N LS10145-002FK-E:A 3/12/2021
65
6.3 Voice Options
6.3.1 Edit Timers
1.
Enter the Installer Code. The panel will automatically access the Main Menu.
2.
Select 6 for the Network Programming.
3.
Select 7 for the Voice Options.
4.
Choose the Site.
5.
Select 1 for the Edit Timers.
Control Lockout
The Control Lockout countdown timer is set to the programmed value when an LOC gains the Fike Series, ECS Control. The
timer starts over upon any key press at the Fike Series, ECS Control LOC. While the Control Lockout Timer is active, an LOC
of equal priority must request the Fike Series, ECS control. The Control Lockout Timer is cleared when the Fike Series, ECS
Control is relinquished. The Control Lockout Timer does not apply to the Fike Series, ECS Super User control.
Select Immediate/Timer/Never
Range 0-720 min/0-59 sec
Auto Reset Fike Series, ECS MIC Triggered Event
If the Timer is selected, the event will automatically reset after being active for the programmed time. If the Event Disabled is
selected, the event will not be allowed to activate from an LOC Station. Selecting Never will require an Emergency System
reset to be performed to reset the event.
Select Never/Timer/Event Disabled, Range from 1-240 min
6.3.2 Edit Voice Commands
When you select a Voice Output Group to be activated by a zone, the cadence pattern choice does not apply. For the Voice Out-
put Groups, one of six System-wide voice commands will activate instead of the cadence pattern.
1.
Enter the Installer Code. The panel will automatically access the Main Menu.
2.
Select 6 for the Network Programming Menu.
3.
Select 7 for the Voice Options.
4.
Choose the Site.
5.
Select 2 for the Edit Voice Commands.
6.
Select the command you want to edit.
Fike Series, ECS Timer
Option
Control Lockout
Immediate/Timer/Never
Auto Reset ECS MIC Triggered Event
Never/Timer/Event Disabled
Auto Reset ECS Event 1
Never/Timer/Event Disabled
Auto Reset ECS Event 2
Never/Timer/Event Disabled
Auto Reset ECS Event 3
Never/Timer/Event Disabled
Auto Reset ECS Event 4
Never/Timer/Event Disabled
Auto Reset ECS Event 5
Never/Timer/Event Disabled
Auto Reset ECS Event 6
Never/Timer/Event Disabled
Auto Reset ECS Event 7
Never/Timer/Event Disabled
Auto Reset ECS Event 8
Never/Timer/Event Disabled
Table 6.3 Auto Reset ECS MIC Triggered Event Timer Menu
System Event
Fire Alarm
Fire System Aux 1
Fire System Aux 2
Fire Zone Aux 1
Fire Zone Aux 2
Fire Pre Alarm
Emergency Communication 1
Emergency Communication 2
Emergency Communication 3
Emergency Communication 4
Emergency Communication 5
Emergency Communication 6
Emergency Communication 7
Emergency Communication 8
Fire Supervisory
System Alert 1-5
Table 6.4 Voice Command Mapping
.