Wiring Requirements for SLC Devices
Fike and SWIFT SLC Device Installation
FCP-300/FCP-300ECS Manual —
P/N LS10145-002FK-E:A 3/12/2021
71
Figure 7.2 Calculating Wire Run Length for a T-tap
7.4.3 Wiring FIK-6815 in Style 6 & 7 (Class A) Configuration
Figure 7.3 illustrates how to wire the SLC loop for the Class A installations.
Figure 7.3 Class A SLC Configuration
NOTE 1:
Style 6 does not use short circuit isolator devices.
NOTE 2:
Style 7 requires an isolator module as the first device on the in and the out loop.
NOTE 3:
No t-taps allowed on class A SLC loops.